30
4-2. Service Operation
4-2-1. Special Operation
▶
Key input of the outdoor unit when the service enters the operation mode.
K1 (Number of press)
KEY operation
Display on 7-Segment
1times
Refrigerant charging in Heating mode
“ ” “ ” “ ” “ ”
2times
Trial operation in Heating mode
“ ” “ ” “ ” “ ”
3times
Refrigerant discharging in Heating mode
“ ” “ ” “ ” “ ”
4times
Disuse
“ ” “ ” “ ” “ ”
5times
Disuse
“ ” “ ” “ ” “ “
6times
Disuse
“ ” “ ” “ ” “ ”
7times
Vacuum
“ ” “ ” “ ” “ ”
8times
Disuse
“ ” “ ” “ ” “ ”
9times
Disuse
“ ” “ ” “ ” “ ”
10times
Disuse
“ ” “ ” “ ” “ ”
11times
Disuse
“ ” “ ” “ ” “ ”
12times
End KEY operation
-
K2 (Number of press)
KEY operation
Display on 7-Segment
1times
Refrigerant charging in Cooling mode
“ ” “ ” “ ” “ ”
2times
Trial operation in Cooling mode
“ ” “ ” “ ” “ ”
3times
Pump down all units in Cooling mode
“ ” “ ” “ ” “ ”
4times
Auto trial operation
“ ” “ ” “ ” “ ”
5times
Checking the amount of refrigerant
“ ” “ ” “x” “x”
(Display of last two digits may differ
depending on the progress)
6times
Discharge mode of DC link voltage
“ ” “ ” “ ” “ ”
7times
Forced defrost operation
“ ” “ ” “ ” “ ”
8times
Forced oil collection
“ ” “ ” “ ” “ ”
9times
Inverter compressor 1 check
“ ” “ ” “ ” “ ”
10times
Inverter compressor 2 check
“ ” “ ” “ ” “ ”
11times
Fan 1 check
“ ” “ ” “ ” “ ”
12times
Fan 2 check
“ ” “ ” “ ” “ ”
13times
End KEY operation
-
▶
To use key operating function for service and maintenance when installing module/group, set as main control or cancel in module/group.
(Body control settings : Hydro control Dip S / W 1 times On,
Modules / How to ungroup : Modular Controller Installation Manual Reference)
▶
During Discharging mode, voltage of Inv1 and Inv2 will be displayed alternately.
▶
Even when the power is off, it is dangerous when you come in contact with inverter PCB, fan PCB since high pressure
DC voltage is charged to those parts.
▶
When replacing or repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/
repairing them. - Wait for more than 15 minutes to allow those parts to be fully discharged.
▶
When there is error, Discharge mode of DC link voltage may not have been effective. Especially when E464 and E364
error is displayed, power element might be damaged so do not use the Discharge mode of DC link voltage.
Summary of Contents for AG042KSVANH
Page 111: ...107 5 6 ASSY PCB MAIN HUB Model All models name is commonness DC 1 2 3 4 5 6 7 8 9 10 11 12 ...
Page 113: ...109 ASSY PCB MAIN HUB cont Model All models name is commonness AC 1 1 2 3 4 5 6 7 8 9 10 11 ...
Page 115: ...111 5 7 ASSY PCB INVERTER PF 8 Model AG042 056KSV666 Series 4 2 3 5 1 8 9 7 6 ...
Page 117: ...113 ASSY PCB INVERTER PF 9 cont Model AG070KSV666 Series 10 8 4 9 7 6 11 12 13 1 2 3 5 ...