31
□
Trial Operation
▶
After initial installation, stable operation for a certain period of time limited to operation conditions.
Cooling
Heating
Method of Entry
K2 Tact Switch 2times
K1 Tact Switch 2times
Compressor
Normal operation, but the maximum frequency limit (differ by model)
Fan and Valves
Normally control conduct
Operation time
Min : 60 minutes, Max : 10 hours
Etc.
∙ Exceed the maximum operating time at stops and waits.
∙ Protection and control, self-diagnosis is performed.
□
Refrigerant Filling Operation
▶
Operation to filling the refrigerant compressor was fixed at a certain frequency.
Cooling
Heating
Method of Entry
K2 Tact Switch 1times
K1 Tact Switch 1times
Compressor
Starting frequency (Mild Start frequency) operation
Fan and Valves
Normally control conduct
Maximum Operation time
60minutes
Etc.
During the filling operation does not enter the special operation, such as oil recovery, defrost.
□
Vacuum Operation
▶
Operation to facilitate vacuum to open the valve after the Outdoor Unit repair.
□
Discharge mode Operation
▶
Block the Inverter PCB 3-phase relay after connected the power, and through compressor, DC voltage is discharging.
- Discharge Mode Operation Process : Push K2 button 6 times shortly.
- INV1 and INV2 DC voltage during discharge mode are displayed alternately.
- Discharge mode Display (Rotate the three page display, as shown below.)
' ' ' ' ' ' ' ‘
→
DC Link Volt1 ( For example, 120[V] 0 1 2 0 display)
→
DCLinkVolt2 ( For example, 120[V] 0 1 2 0 display)
→
' ' ' ' ' ' ' ‘
→
DC Link Volt1 …
▶
If want operation again after complete discharge mode : Restart after K3 key to Reset or Power Reset.
Method of Entry
K1 Tact Switch 7times
Compressor
OFF
Fan
OFF
4WAY Valve
OFF
Valves
Open all valves maximum
Etc.
If not turn off the vacuum mode, the start of normal operation is prohibited.
Summary of Contents for AG042KSVANH
Page 111: ...107 5 6 ASSY PCB MAIN HUB Model All models name is commonness DC 1 2 3 4 5 6 7 8 9 10 11 12 ...
Page 113: ...109 ASSY PCB MAIN HUB cont Model All models name is commonness AC 1 1 2 3 4 5 6 7 8 9 10 11 ...
Page 115: ...111 5 7 ASSY PCB INVERTER PF 8 Model AG042 056KSV666 Series 4 2 3 5 1 8 9 7 6 ...
Page 117: ...113 ASSY PCB INVERTER PF 9 cont Model AG070KSV666 Series 10 8 4 9 7 6 11 12 13 1 2 3 5 ...