1
3
4
No.
D
e
s
c
ription
1
Select operation On/Off input method of module/group
2
Select temperature setting input method of module/group
3
Select operation mode (Cool/Heat, Hot water/Cool storage) input method of module/group
4
Select demand control input method of module/group
5
Select demand level
• Current will be limited below the set level when "Perform" command is transmitted.
6
quiet function input method of module
7
Select forced fan function input method of module
• Forced fan: Removes accumulated snow by operating the fan of stopped unit in low frequency
• Snow accumulation prevention, which operates occasionally when outdoor temperature is below zero, is basic function.
8
Select water law input method of module/group
9
Select pump operation status when thermo OFF
10
Select to use error clear function by external contact
11
Setting CHILLER unit address: identical with channel address used by DMS
12
Select quiet function level
• Quiet function will start in set level when "Perform" command is transmitted.
• Level comparison: Level3 > Level2 > Level1
13
Confirm delay for unsecured flow rate when operating: Delay for inspecting no input for pump interlock and unsecured flow rate
• Compressor will not operate until water flow is detected.
14
Set when controlling water outlet temperature by installing extra water temperature gauge on water pipe header or tank
• External water outlet temperature sensor should be installed on main unit of group (or module when group is not available).
• Standard for water outlet temperature depends on external water outlet temperature sensor except when operation pattern is
standard control.
15
Setting water law standard
• To set room temperature as stnadard, external room temperature sensor should be installed.
• Room temperature sensor should be installed on main unit of group (or module when group is not available).
16 ~ 27
Water law control constant: Refer to water law operation graph.
28
Recognition of external control operation ON/OFF
• 0 (recognizing usual signal): Constantly inspects ON/OFF status of contact and set operation ON/OFF
• 1 (recognizing instant signal): Set operation ON/OFF when contact ON/OFF signal is input (when external contact is consisted of
button click)
34
Select to use low temperature function
• The function will operate when set simultaneously with product option of module control (Seg23 of installation option 02 = 'E')
• Low temperature function: Expands water outlet usage range in Cool/Cool stoarge mode ( 5 ~ 25 °C
ĺ
-10 ~ 25 °C)
• When using low temperature function, use brine and maintain the concentration under freezing point.
Function description
Summary of Contents for AG042KSVANH
Page 111: ...107 5 6 ASSY PCB MAIN HUB Model All models name is commonness DC 1 2 3 4 5 6 7 8 9 10 11 12 ...
Page 113: ...109 ASSY PCB MAIN HUB cont Model All models name is commonness AC 1 1 2 3 4 5 6 7 8 9 10 11 ...
Page 115: ...111 5 7 ASSY PCB INVERTER PF 8 Model AG042 056KSV666 Series 4 2 3 5 1 8 9 7 6 ...
Page 117: ...113 ASSY PCB INVERTER PF 9 cont Model AG070KSV666 Series 10 8 4 9 7 6 11 12 13 1 2 3 5 ...