Setting the pre-pressure of the expansion vessel
When it is required to change the default pre-pressure of the expansion vessel(1 bar), keep in mind the
following guidelines:
X
Use only dry nitrogen to set the expansion vessel pre-pressure.
X
Inappropriate setting of the expansion vessel pre-pressure will lead to malfunction of the system.
Therefore, the pre-pressure should only be adjusted by a licensed installer.
Installation height
difference
(a)
Water volume
< 220 Litres
> 220 Litres
<7m
No pre-pressure adjustment required.
Actions required:
t1SFQSFTTVSFNVTUCFEFDSFBTFEDBMDVMBUF
according to
“Calculating the pre-pressure of the expansion
vessel”.
t$IFDLJGUIFXBUFSWPMVNFJTMPXFSUIBO
maximum allowed water volume
>7m
Actions required:
t1SFQSFTTVSFNVTUCFJODSFBTFEDBMDVMBUFUIF
appropriate value following by “Calculating the
pre-pressure of the expansion vessel”.
t$IFDLJGUIFXBUFSWPMVNFJTMPXFSUIBO
maximum allowed water volume
Expansion vessel of the unit too small for the
installation.
(a) Installation height difference: height difference(m) between the highest point of the water circuit and the indoor unit. If the
indoor unit is located at the highest point of the installation, the installation height is considered 0m.
Calculating the pre-pressure of the expansion vessel
The pre-pressure(Pg) to be set depends on the maximum installation height difference(H) and is calculated
as below:
Pg=(H/10+0.3) bar
Water volume (Litre) in total system including pipes
[L
it
]
50
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
100
150
200
250
300
350
400
Operation range
Expansion Vessel capacity (Liter)
Norminal
X
Water volume of total system for reliable performance is minimum 50 litres.
Pipe work (Continued)
Summary of Contents for AEN160YDEHA
Page 1: ......
Page 11: ...E 11 ENGLISH Dimensional drawing 131 7 78 5 103 7 104 0 125 0 490 22 0 39 2 850 0 510 0 314 6 ...
Page 22: ...E 22 Wiring diagram AEN160YDGHA Wiring work Continued ...
Page 23: ...E 23 ENGLISH Wiring diagram AEN160YDEHA AEN080YDEHA ...
Page 38: ...E 38 DHW tank Continued Accessories Leg 3 Anode bar 1 Conduit 1 ...
Page 48: ......