54
EB 8389 EN
Statistical information
−
Required transit time OPEN (Code 21):
Variable
−
Required transit time CLOSED (Code 22):
Variable
Based on the operating point, the test is per-
formed with a change in travel of less than
1 % to find the change in drive signal (∆y).
The changes in drive signal ∆y are classified
according to the valve position x in the valve
position classes. The average value ∆y per
valve position class is calculated from all the
values and plotted in a graph (Measure-
ment).
−
If the test is started in manual mode using
the setting 'Enable time distance' = 'User
defined' and another test is active at the
time selected, the hysteresis test starts 30
seconds after the active test ends.
−
A straight line from the average reference
data is shown in cases where no data
could be compiled for valve working rang
-
es which were not covered by the long-
term monitoring.
−
If the hysteresis test could not be completed
because the valve position is at the top or
bottom limit of the working range, the po
-
sitioner generates the message (Test infor
-
mation) 'Test at operating point not possi
-
ble'.
Short-term monitoring
To provide a short-term trend, the last ten
valve positions x
and the associated changes
in
drive signal (∆y)
values are saved in the
'Short-term' folder.
Requirements
1. A single-acting actuator is mounted on
the valve.
2. No booster is mounted on the control
valve.
3. The valve operates as a control valve.
4. A reference test has been performed (see
section 2.4.1).
1.
Settings > Identification > Positioner > Actu
-
ator
−
Model:
Single acting
, [-/-]
2.
−
Booster:
Not present
, [-/-]
3.
Start-up
−
Application type
1)
(Code 49 - h0): [Control
valve]
1)
Setting cannot be made in Type 3730-4. In
this case, the application type = Control valve
Defining parameters
1.
Select classification for status messages.
2. Set cancellation condition (see sec-
3.
Define start conditions.
4. Start hysteresis test.
The 'Test information' status indicates
'Running test'. 'd5' and 'tESt' are indicat-
ed in alternating sequence on the posi-
tioner display. 'Function check' is acti-
vated as the condensed state.
Types 3730-2/-3/-4/-5 (1.5x) and Type 3731-3: