108
EB 8389 EN
Binary input
issued in the BINARY_INPUT2 parameter
of the AO Transducer Block.
−
Internal solenoid valve
In this setting, the current switching state
of the optional internal solenoid valve is
analyzed and issued over OUT_D. '0' in-
dicates a de-energized solenoid valve (U
< 15 V DC) and '1' an energized sole
-
noid valve (U > 19 V DC).
−
Discrete final valve position
In this setting, the current discrete valve
position is issued over OUT_D. The val-
ues are assigned as follows:
0
Device not initialized
1
Valve closed
2
Valve open
3
Valve in intermediate position
−
Condensed state
In this setting, the current condensed
state according to NAMUR Recommen-
dation NE 107 is issued over OUT_D.
The status messages are assigned to the
discrete value as follows:
0
No message
1
Maintenance required
2
Maintenance demanded
3
Maintenance alarm
7
Function check
−
Condensed state and VST
The positioner starts a single partial
stroke test. The test is performed using
the settings in Code 49 - d2 to Code 49
- d9 (see section 5.4).
Additionally, the condensed state ac-
cording to NAMUR Recommendation
NE 107 is issued over OUT_D. The status
messages are assigned to the discrete
value as follows:
0
No message
1
Maintenance required
2
Maintenance demanded
3
Maintenance alarm
7
Function check
The logic state of the binary input is defined
in the 'Configuration binary input 2' param
-
eter (CONFIG_BINARY_INPUT_2).
Settings > Binary input 2 (DI2, TRD)
−
Selection binary input 2: [Floating contact], In-
ternal solenoid valve, Discrete final valve posi
-
tion, Condensed state, Condensed state and
VST
−
Configuration binary input 2: [Not evaluated],
Actively open, Actively closed, Actively open –
leakage detection, Actively closed – leakage
detection, Start PST
−
Assignment TRD/DI: [Connected with DI2
TRD (2)], Not connected with TRD (0)
Summary of Contents for TROVIS 3730-3
Page 6: ...6 EB 8389 EN...
Page 43: ......
Page 57: ......
Page 83: ...EB 8389 EN 83...
Page 130: ...130 EB 8389 EN...