112
EB 8389 EN
Appendix
Code
No.
Parameter
– Readings/
values [default setting]
Description
Codes with marked with an asterisk (*) must be enabled with Code
3
prior to configuration.
49* d3
Step stop
0.0 to 100.0 %,
[90.0 %]
1), 2), 3)
[95 %]
4), 5)
Stop value for step response
d4
Activation of ramp
function
[No]
1), 2), 3), 5)
[YES]
4)
Activates or deactivates ramp function.
d5
Ramp time (rising)
0 to 9999 s,
[15 s]
1), 2)
[45 s]
4), 5)
, [60 s]
3)
Ramp time for 0 to 100 % travel (rising) of ramp function
Initialization provides a sensible value that is not to be undercut, if
possible.
d6
Ramp time (falling)
0 to 9999 s,
[15 s]
1), 2)
[45 s]
4), 5)
, [600 s]
3)
Ramp time for 100 to 0 % travel (falling) of ramp function
Initialization provides a sensible value that is not to be undercut, if
possible.
d7
Settling time before test
start
1.0 to 240.0 s,
[10.0 s]
1), 2)
[2 s]
4), 5)
, [1 s]
3)
Waiting time before test is started to ensure that value for step start
can be reached safely.
d8
Delay time after step
1.0 to 240.0 s
1), 2), 3)
,
2.0 to 100.0 s
4)
,
0.1 to 240.0 s
5)
,
[2.0 s]
Waiting time between first step change and start of second step
change
d9
Scan rate
0.2 to 250.0 s,
[0.2 s]
1), 2), 4), 5)
,
[0.8 s]
3)
Scan rate of step response measurement