22
EB 8389 EN
Monitoring
The condensed state is marked by until
the positioner data have been uploaded.
Diagnostics > Status messages
−
Condensed state (Code 48 - d6)
The condensed state can be read in the posi-
tioner display in Code 48 - d6 (see Table 3).
3.2.1 Condensed state at the
fault alarm output
3730-2 3730-3 3731-3 3730-4 3730-5 3731-5
•
•
•
In positioners with a fault alarm output, the
condensed state can also be read out at the
fault alarm output if one of the following
conditions occurs:
1. Condensed state 'Maintenance alarm' is
activated.
2. Condensed state 'Function check' is acti-
vated and the fault alarm output is acti-
vated.
3. Condensed state 'Maintenance required'
is activated and the fault alarm output is
activated.
2.
Settings > Positioner > Error control
−
Fault alarm at condensed state 'Function
check' (Code 32):
[Yes]
3.
−
Fault alarm at condensed state 'Mainte-
nance required' (Code 33)
: [Yes]
Note
3.3 Logging
The last 30 generated messages are saved in
the positioner with a time-stamp (logged by
the operating hours counter).
You can view these messages in TROVIS-
VIEW in the Diagnosis folder (> Status
messages > Logger).
−
If the positioner is fitted with a solenoid
valve, a triggering of the solenoid valve
can only be logged when 'Logging of int.
solenoid valve' is activated.
−
In the event the solenoid valve is triggered
again, this is only logged when the 'Min.
clearance new logging int. solenoid valve'
has elapsed since the last triggering.
Settings > Positioner > Error control
−
Logging of int. solenoid valve
1)
: [Yes], No
−
Min. clearance new logging int. solenoid valve
1)
:
0 to 5000 s, [300 s]
1)
Not Type 3730-4
Note