EB 8389 EN
125
Appendix
Message
Possible reasons
Recommended action
Status
classifica
-
tion
Single reset
Working range
−
The working range is
mainly close to the
CLOSED/max. OPEN
position.
−
The working range is
mainly in the CLOSED/
max. OPEN position.
Rethink the working range.
•
[ ]
•
Section 4.3.2
Friction
−
The friction is much high-
er/lower over the entire
working range.
−
The friction is much high-
er/lower over a section.
Check the valve's packing.
•
[ ]
•
Section 4.7.2,
section 5.2.2
Actuator springs
−
The spring stiffness is re-
duced (spring failure).
−
Reduced spring compres-
sion
−
The actuator springs are
working at full capacity.
Check actuator springs.
•
[ ]
•
Section 4.6.2,
section 5.1.2
Inner (seat) leakage
Alarm limit 2 or 3 exceeded.
Check seat and plug.
•
[ ]
•
Section 7.1.2.4
Seat leakage exists.
•
Section 4.4.2
External leakage
External leakage may possibly
exist or is to be expected soon.
Check the valve's packing.
•
[ ]
•
Section 4.5.2
External leakage is perhaps
soon expected.
•
Section 4.7.2
PST/FST
The partial stroke test or the
full stroke test has not been
completed successfully.
Check test cancellation condi-
tions. See section 5.4 and
section 5.5.
•
[ ]
•
Section 5.4.4,
section 4.5.2
Summary of Contents for TROVIS 3730-3
Page 6: ...6 EB 8389 EN...
Page 43: ......
Page 57: ......
Page 83: ...EB 8389 EN 83...
Page 130: ...130 EB 8389 EN...