EB 8389 EN
113
Appendix
Code
No.
Parameter
– Readings/
values [default setting]
Description
Codes with marked with an asterisk (*) must be enabled with Code
3
prior to configuration.
E Cancellation conditions of the partial stroke test (PST)
E0
Activation x control
[No]
1), 2), 3)
[YES]
4), 5)
Activates or deactivates x control.
49* E1
x control value
–10.0 to 110.0 % of
total travel, [0.0 %]
1),
2), 3)
[85.0 %]
4), 5)
The test is canceled when the valve position
– falls below the adjusted value (step end < step start)
– exceeds the adjusted value (step end > step start)
E2
Unassigned
E3
Unassigned
E4
Unassigned
E5
Activation PST
tolerance band control
[No], YES
Activates or deactivates PST tolerance band monitoring.
E6
PST tolerance band
0.1 to 100.0 %,
[5.0 %]
The test is automatically canceled as soon as the Step end (Code 49
- d3) exceeds this percentage.
E7
Max. test duration,
user-defined
30 to 25000 s,
[30 s]
1), 4), 5), 6)
[90 s]
2), 3)
Maximum time within which a test can be completed before the test
is canceled automatically.
F Partial stroke test (PST) information · Read only
F0
No test available
No test available or test canceled manually.
F1
Test OK
F2
x cancellation
The test was canceled by x cancellation function.
F3
y cancellation
The test was canceled by y cancellation function.
F4
Tolerance band
exceeded
The test was canceled. The x-values are outside the tolerance band.
1)
Type 3730-2
2)
Type 3730-3
3)
Type 3731-3
4)
Type 3730-4
5)
Type 3730-5
6)
Type 3731-5