80
EB 9510 EN
Annex
Menu
Adjustment range/values/description
Unit
... .15
Unit in which the measured value is to be indicated.
▪
Selectable units:
% · kg · Nm³ · L · ft³ · lbs · mbar · bar · kPa · psi · mmH
2
O ·
cmH
2
O · mH
2
O · inH
2
O · °C · °F · K
Lower measuring range
value
... .16
Determine the lower limit of the measuring range at 4 mA
(depending on the selected unit)
Upper measuring range
value
... .17
Determine the upper limit of the measuring range at 20 mA
(depending on the selected unit)
Event: Broken cable
... .18
Activates or deactivates the event for a detected cable
breakage at the input of the AI option module. The event is
activated when the signal falls below the switching threshold of
0.2 mA.
▪
ON (default)
▪
OFF
Event: Residual current
... .19
Activates or deactivates the event for a detected residual
current violation at the input of the AI option module. The event
is activated when the signal falls below the switching threshold
of 3.6 mA or exceeds 21.0 mA.
▪
ON (default)
▪
OFF
Limit 1
... .20
Activate/deactivate limit 1
▪
ON (default)
▪
OFF
Mode
... .21
An upper limit can be determined with 'Max. contact' and a
lower limit with 'Min. contact' for limit 1.
▪
Max. contact
▪
Min. contact
Limit
... .22
Setting limit 1
▪
The limit is set in % when the signal source parameter is set to
‘Unknown’ or ‘Filling level’.
Limit
... .23
Setting limit 1
▪
The limit is set in % when the signal source parameter is set to
‘Unknown’ or ‘Filling level’.
Limit 2
... .24
Activate/deactivate limit 2
▪
ON (default)
▪
OFF