![Samson Media 7 Mounting And Operating Instructions Download Page 26](http://html.mh-extra.com/html/samson/media-7/media-7_mounting-and-operating-instructions_805914026.webp)
26
EB 9510 EN
Design and principle of operation
Communication
Local
SAMSON SSP interface and serial interface adapter, TROVIS-VIEW
Remote data transmission
GSM module
Weight
Device without valve block
Approx. 3300 g
Device with valve block (without
pressure gauge)
Approx. 5200 g
Table 2:
Power supply
Optional power supply
Two-wire version
5007-1-
000
0
5007-1-
110
0
5007-1-
111
0
5007-1-
120
0
5007-1-
121
0
Explosion protection No explosion
protection
ATEX Ex ia
IECEx Ex ia
ATEX Ex ia
IECEx Ex ia
Output
4 to 20 mA
Permissible load R
B
in Ω
R
B
= (U
B
– 12 V)/0.020 A
Output circuit
–
Intrinsically safe according to EN/IEC 60079-11
Power supply U
B
for two-wire
transmitter
12 to 36 V DC 12 to 28 V DC (only in conjunction with an intrinsically safe circuit)
24 V version
5007-1-
000
1
Input voltage
24 to 36 V DC
Output voltage
12 V DC
Power
24 W
Version
Reverse polarity protection
Table 3:
Optional additional functions
AO: Analog output
Version
Two-wire system, galvanic isolation, reverse polarity protection, reversible direction
of action
Power supply
10 to 30 V DC
Output signal
4 to 20 mA
Operating range
3.8 to 20.5 mA (according to NAMUR Recommendation NE 43)
Error indication
3.4 or 21.6 mA
No-load current
1.36 mA
Static destruction limit
38 V DC · 30 V AC
Summary of Contents for Media 7
Page 88: ...88 EB 9510 EN Annex ...
Page 89: ...EB 9510 EN 89 ...
Page 90: ...90 EB 9510 EN ...
Page 91: ...EB 9510 EN 91 ...
Page 92: ...92 EB 9510 EN ...
Page 93: ...EB 9510 EN 93 ...
Page 94: ......
Page 95: ......