EB 9510 EN
79
Annex
Menu
Adjustment range/values/description
Assignment of analog
output
... .9
Assignment of a measured value for the analog output (in
differential pressure mode)
▪
Differential pressure
▪
Tank pressure (pressure sensor), only when pressure sensor
exists
Pressure at 20 mA
... .10
The adaptation to the tank can be made when a pressure
sensor is used.
▪
0 to 60 bar (based on 20 mA)
Signal of analog output
... .11
Read the applied signal in %
Start test
... .33
Executable function: two-wire test signal issued.
Test mode
... .34
Test mode is
Active
while the test is in progress (test duration:
30 s).
▪
Not active
▪
Active
Test signal of analog
output
... .35
Test signal in % based on the 4 to 20 mA signal range.
▪
–10.00 to +110.00 %
AI: Analog input/AIA: Analog input active
Option module
identification
... .1
Detection of optional additional function: AI: Analog input
Option module status
... .2
Read the current status of the option module
▪
No module inserted
▪
Module not permissible in this setup
▪
Module unknown
▪
Module active
Name
... .3
Enter a name (max. 15 characters) for identification.
Signal source
... .12
Enter the signal source on which the 4 to 20 mA signal is
based
▪
Unknown (default)
▪
Filling level
▪
Pressure
▪
Temperature
Medium identifier
... .13
Enter a name (max. 15 characters) to identify the medium.
▪
Enter characters as required (default: MEDIUM)
Measured value
... .14
Read the current measured value in the selected unit
Summary of Contents for Media 7