68
EB 8390 EN
Parameter list
No.
Error message
Possible causes
E5*
INIT: no switching volt-
age applied
•
Incorrect voltage supplied to the solenoid valve
•
Forced venting active during initialization
Recommended action
•
Check switching voltage to integrated/external solenoid
valve.
•
Check forced venting input.
E6*
INIT: time-out
•
Supply pressure too low
•
Friction too high
• K
V
coefficient of solenoid valve too low
Recommended action
•
Check attachment and supply air line.
•
Version for external solenoid valve:
Use a different solenoid valve with a higher K
V
coefficient.
E7*
Function canceled
•
Internal error
Recommended action
•
Repeat function/initialization.
E8*
Unable to calibrate
end positions
• The end stops have shifted by 10° at the minimum.
Recommended action
•
Re-initialize the electronic limit switch.
Device error
E9*
Device error 1
•
Internal error
Recommended action
•
Restart the electronic limit switch (return it to SAMSON if er-
ror repeatedly occurs).
Note:
When E9 is generated, the wire break (contact B_LB) is additionally signaled in
accordance with DIN EN 60947-5-6.
E10*
Device error 2
•
Internal error
Recommended action
•
The electronic limit switch should be replaced soon. The de-
vice still functions.
Summary of Contents for 3738-20
Page 69: ...EB 8390 EN 69 Dimensions in mm 14 Dimensions in mm 231 20 17 97 130 185 84 42 10 30 40...
Page 71: ...EB 8390 EN 71...
Page 72: ...72 EB 8390 EN...
Page 73: ...EB 8390 EN 73...
Page 74: ...74 EB 8390 EN...
Page 75: ...EB 8390 EN 75...
Page 76: ...76 EB 8390 EN...
Page 77: ...EB 8390 EN 77...
Page 80: ...80 EB 8390 EN...
Page 81: ...Key number 42...