52
EB 8390 EN
Operation
9.2.2
Starting the partial
stroke test
A single PST test can be started manually or
a regular PST test can be started automati-
cally at defined time intervals.
Start PST automatically at defined intervals
(RUN mode)
The test is performed automatically after a
time interval (days) entered in
P16
('Auto-
matic PST).
NOTICE
The automatic test causes the valve to
leave its operating position without a
switching demand.
Note:
The default setting OFF causes the
automatic test to be deactivated.
P16
: Start automatic PST
Turn
g
P16
Press ,
P16
blinks
Turn
g
Required time period [days]
Press
to confirm the entry and to exit the
parameter.
Start PST manually (SET or RUN configura-
tion mode)
A single test is started by the
P17
parameter.
P17:
Reading before the
partial stroke test
starts
After the partial stroke
test starts:
P17
: Start of PST is be-
ing prepared
P17
: Test in progress
Turn
g
P17
(PST)
Press and hold for six seconds.
The seconds remaining until the test starts
appear on the display.
The test starts (display: blinking PST).
Note:
−
A test in progress can be canceled
by pressing the rotary pushbutton
( ).
ESC appears on the display.
−
A canceled partial stroke test (PST)
is logged with a time stamp in
TROVIS-VIEW.
Summary of Contents for 3738-20
Page 69: ...EB 8390 EN 69 Dimensions in mm 14 Dimensions in mm 231 20 17 97 130 185 84 42 10 30 40...
Page 71: ...EB 8390 EN 71...
Page 72: ...72 EB 8390 EN...
Page 73: ...EB 8390 EN 73...
Page 74: ...74 EB 8390 EN...
Page 75: ...EB 8390 EN 75...
Page 76: ...76 EB 8390 EN...
Page 77: ...EB 8390 EN 77...
Page 80: ...80 EB 8390 EN...
Page 81: ...Key number 42...