60
EB 8390 EN
Parameter list
13
Parameter list
No.
Parameter – Readings,
values [default setting]
Description
Parameters marked with an asterisk (*) can only be changed when the electronic limit switch is in the
SET configuration mode (set in P2).
P0
Info: actual value
After initialization:
current valve position in %
Keep
pressed down
g
current valve position
in ° (angle)
Before initialization:
Travel in °
See sec-
P1
Reading direction
1234 ·
1234
· ESC
The reading direction of the display is turned by
180°.
See sec-
Start-up
P2
Configuration
RUN · [SET] · ESC
RUN:
Operation mode, parameter settings
cannot be changed
SET:
Configuration mode (no operation), pa
-
rameter settings can be changed,
, icons,
F15
status message generated
See
P3
Verify LCD segments
TSTD, 0000 to 9999
Read only
See sec-
P4*
Actuator type
[ROT] · LIN · ESC
ROT:
Rotary actuator
LIN:
Linear actuator
See sec-
After initialization, this parameter is locked and can first be selected and
changed after performing a reset to default settings (P21).
P5*
Actuator's direction of action
[PTO] · PTC · ESC
PTO (power to open):
Fail-safe position = Valve CLOSED, 0 % of
travel range
Operating position = Valve OPEN, 100 %
of travel range
PTC (power to close):
Fail-safe position = Valve OPEN, 100 % of
travel range
Operating position = Valve CLOSED, 0 % of
travel range
See sec-
Note:
Observe the assignment depending on the direction of action (see
After initialization, this parameter is locked and can first be selected and
changed after performing a reset to default settings (
P21
).
Summary of Contents for 3738-20
Page 69: ...EB 8390 EN 69 Dimensions in mm 14 Dimensions in mm 231 20 17 97 130 185 84 42 10 30 40...
Page 71: ...EB 8390 EN 71...
Page 72: ...72 EB 8390 EN...
Page 73: ...EB 8390 EN 73...
Page 74: ...74 EB 8390 EN...
Page 75: ...EB 8390 EN 75...
Page 76: ...76 EB 8390 EN...
Page 77: ...EB 8390 EN 77...
Page 80: ...80 EB 8390 EN...
Page 81: ...Key number 42...