56
EB 8390 EN
Operation
The electronic limit switch must be in the con-
figuration mode (SET). See page 40.
Display when P6 = NC
P19:
Reading before the
test starts
After the test has started:
P19
: Simulation of
contact A
(limit switch for fail-
safe position)
P19
: Simulation of
contact B
(limit switch for
operating position)
P19
: Simulation of wire
break at contact B
P19
: Simulation of
contact C:
(signal on reaching
target range during
partial stroke test)
P19
: Simulation of fault
alarm contact
Turn
g
P19
(TSTC)
Press ,
P19
blinks
Turn
g
A/B/B_LB/C/St
All contacts are activated.
Press .
The contact selected is deactivated while the
rotary pushbutton is pressed.
Turn
g
ESC
Press to exit the parameter setting.
Note:
When
P6
= NO, the logic for con
-
tacts A, B and C is reversed. B_LB on
the display means the contact C is
activated.
9.4
Testing the solenoid valve
You can de-energize the solenoid valve while
the voltage is still applied using the
P20
pa-
rameter. In this case, the valve moves to the
fail-safe position.
Observe the assignment of contacts A and
B depending on the direction of action
The electronic limit switch must be in the con-
figuration mode (SET). See page 40.
P20:
Reading before the
test starts
After the test has started:
P20
: Testing solenoid
valve
Example: PTO
%
Turn
g
P20
(TSTS)
Press ,
P20
blinks and
ESC
is displayed.
Summary of Contents for 3738-20
Page 69: ...EB 8390 EN 69 Dimensions in mm 14 Dimensions in mm 231 20 17 97 130 185 84 42 10 30 40...
Page 71: ...EB 8390 EN 71...
Page 72: ...72 EB 8390 EN...
Page 73: ...EB 8390 EN 73...
Page 74: ...74 EB 8390 EN...
Page 75: ...EB 8390 EN 75...
Page 76: ...76 EB 8390 EN...
Page 77: ...EB 8390 EN 77...
Page 80: ...80 EB 8390 EN...
Page 81: ...Key number 42...