EB 8390 EN
67
Parameter list
13.2
Error messages
No.
Error message
Possible causes
Error messages marked with an asterisk (*) can be confirmed in SET configuration mode. See sec
-
TROVIS-VIEW:
The last 32 error messages are displayed with a time stamp in TROVIS-VIEW
[Diagnostics – Logging of device errors].
E0
Device not initialized
•
The electronic limit switch has not yet been initialized.
Recommended action
•
Start initialization with P9 or P10 parameter.
E1*
INIT: actuator does not
move
•
Mechanical blockage
•
Supply pressure too low
•
External leakage
•
Incorrect voltage supplied to the solenoid valve
Recommended action
•
Check attachment and supply air line.
•
Check switching voltage to integrated/external solenoid
valve.
E2*
INIT: min. travel not
reached
•
Mechanical blockage
•
Supply pressure too low
•
External leakage
Recommended action
•
Check attachment and supply air line.
•
Increase angle of rotation at the actuator.
E3*
INIT: max. travel ex-
ceeded
• Maximum angle exceeds 170°.
Recommended action
•
Reduce angle of rotation at the actuator.
E4*
INIT: actuator travels
too fast
• K
V
coefficient of solenoid valve too high
Recommended action
•
Install a restriction.
•
Version for external solenoid valve:
Reduce K
V
coefficient at solenoid valve.
Summary of Contents for 3738-20
Page 69: ...EB 8390 EN 69 Dimensions in mm 14 Dimensions in mm 231 20 17 97 130 185 84 42 10 30 40...
Page 71: ...EB 8390 EN 71...
Page 72: ...72 EB 8390 EN...
Page 73: ...EB 8390 EN 73...
Page 74: ...74 EB 8390 EN...
Page 75: ...EB 8390 EN 75...
Page 76: ...76 EB 8390 EN...
Page 77: ...EB 8390 EN 77...
Page 80: ...80 EB 8390 EN...
Page 81: ...Key number 42...