Installation
The work described in this section is only to
be performed by personnel appropriately
qualified to carry out such tasks.
5.1
Installation conditions
Work position
The work position for the control valve is the
front view looking onto the operating con-
trols (including valve accessories).
Plant operators must ensure that, after instal-
lation of the device, the operating personnel
can perform all necessary work safely and
easily access the device from the work posi-
tion.
Pipeline routing
The inlet and outlet lengths (see Table 5-1)
vary depending on several variables and
process conditions and are intended as rec-
ommendations. Contact SAMSON if the
lengths are significantly shorter than the rec-
ommended lengths.
To ensure that the valve functions properly,
proceed as follows:
Î
Observe the recommended inlet and
outlet lengths (see Table 5-1). Contact
Table 5-1:
Inlet and outlet lengths
Q
b x DN
a x DN
b x NPS
a x NPS
State of process
medium
Valve conditions
Inlet length a
Outlet length b
Gas
Ma ≤ 0.3
2
4
Vapor
Ma ≤ 0.3
1)
2
4
Liquid
Free of cavitation/w < 10 m/s
2
4
Cavitation producing
noise/w ≤ 3 m/s
2
4
Cavitation producing
noise/3 < w < 5 m/s
2
10
1)
No wet steam
Q
Flow rate
a
Inlet length
b
Outlet length
Summary of Contents for 3349
Page 6: ...6 EB 8048 2 EN...
Page 15: ...EB 8048 2 EN 1 9 Safety instructions and measures...
Page 16: ...1 10 EB 8048 2 EN...
Page 34: ...4 6 EB 8048 2 EN...
Page 44: ...5 10 EB 8048 2 EN Installation...
Page 52: ...8 4 EB 8048 2 EN...
Page 66: ...9 14 EB 8048 2 EN...
Page 72: ...12 2 EB 8048 2 EN...
Page 74: ...13 2 EB 8048 2 EN...
Page 92: ...14 18 EB 8048 2 EN...
Page 100: ...15 8 EB 8048 2 EN...
Page 101: ......
Page 102: ......
Page 103: ......