background image

 

 

23 

Function 06 Write Single Register & Function 03 Read Holding Registers 

Address  Register name 

Short 

description 

Medium 

description 

Long description 

Max 

value 

Min 

value 

Unit of 

meas. 

Modbus 

Bit pos. 

Modbus 

length 

Default 

value 

200 

LimitAlarm 

Alarm limit 

Alarm threshold 

Alarm threshold 

10000  0 

ppm 

16 

 

201 

Delay 

Delay 

Delay before 
alarm 
activation 

Delay before alarm 
activation 

20 

min 

16 

203 

LimitWarning  Warning limit  Warning 

threshold 

Warning threshold 

10000  0 

ppm 

16 

 

204 

AnalogOutpu
tType 

Type of 
analogue 
output 

Type of analogue 
output 
signal 

2 = 4-20mA ; 5 = 1-
5V ; 8 = 
2-10V ; 10 = 0-10V 

10 

 

16 

205 

PassCode 

PassCode 

Password to 
authorise 
the next 
command 

Password to 
authorise the 
next command 

65535  0 

 

16 

 

206 

GasType (*) 

Type of gas 

Gas type value 

Gas type value 

50 

 

16 

 

655 

SpanConcent
ration 

SpanConcentr
ation 

Span 
concentration for 
calibration 

Span concentration 
for 
calibration 

10000  0 

ppm 

16 

 

Function 02 Read Input Status 

Address  Register name 

Short 

description 

Medium 

description 

Long description 

Max 

value 

Min 

value 

Unit of 

meas. 

Modbus 

Bit pos. 

Modbus 

length 

Default 

value 

300 

PreAlarmFlag  Alarm flag 

Indicator of 
whether the 
alarm threshold 
has 
been exceeded 

1 = alarm threshold 
exceeded 

 

302 

Fault 

Fault 

Fault indication 

1 = Fault activated 

 

303 

W1LED 

W1LED 

W1 RED status 
LED 

W1 RED status LED  1 

 

304 

W2LED 

W2LED 

W2 GREEN status 
LED 

W2 GREEN status 
LED 

 

305 

W3LED 

W3LED 

W3 YELLOW 
status LED 

W3 YELLOW status 
LED 

 

307 

PreWarningFl
ag 

PreWarning 
flag 

Indicator of 
whether the 
warning 
threshold has 
been exceeded 

1 = warning 
threshold exceeded 

 

308 

WarningFlag  Warning 

relay 

Warning 
activation 
indicator 
including delay 

1 = Warning ON 

 

309 

AlarmFlag 

Alarm relay 

Alarm activation 
indica- 
tor including 
delay 

1 = Alarm on 

 

310 

BTStatus 

BTStatus 

Bluetooth status 

1 = Bluetooth on 

 

311 

SensorExpire

Sensor 
expired 

Flag showing if 
the sensor needs 
to be 
replaced 

1 = sensor to be 
replaced 

 

312 

DeviceUnlock
ed 

Device 
unlocked 

Indicator for 
authorisation to 
modify variables 

1 = unlocked 

 

 

Summary of Contents for GLACIAR MIDI

Page 1: ...GLACI R MIDI Gas Leakage Detector for commercial and industrial applications USER MANUAL...

Page 2: ...NETIC KEY FOR CONFIGURATION 17 4 6 1 Bluetooth activation 17 4 6 2 Alarm warning management 17 4 7 SAMON GLACI RAPPFEATURES 18 4 7 1 Connecting the device via Bluetooth 18 4 8 MODBUS NETWORK 21 Parame...

Page 3: ...32 6 2 GASDETECTED 33 6 3 TECHNICALSPECIFICATIONS 34 6 3 1 Mechanical specification 34 6 4 DISPOSALOFTHEDEVICE 35 6 4 1 Disposal of electrical and electronic equipment 35 6 4 2 Disposal of the sensor...

Page 4: ...Store can be used to access the device The GLACI R MIDI series detectors enablecompliance with refrigeration safety standards e g EN 378 ASHRAE 15 through alarms to alert personnel in the event of a...

Page 5: ...5 2 2 Physical dimensions Built in version Remote version...

Page 6: ...ed below are intended as support for installers and not as rules in their own right SAMON accepts no liability for the installation of the gas detectors 3 2 1 Sensor height Gas type Mounting height NH...

Page 7: ...ese spaces the refrigerant gas is usually denser than air consequently the gas detectors should be installed close to the floor Also consider installing the gas detector in ceilings or false ceilings...

Page 8: ...using the app as described below or through the Modbus connection Use the cable glands provided to pass through and connect the cables to the terminals as shown in the figure and in the connection tab...

Page 9: ...J4 1A NO contact for the warning fault relay 2A Common for the warning fault relay 3A NC contact for the warning fault relay J5 1B NO contact for the alarm relay 2B Common for the alarm relay 3B NC c...

Page 10: ...ing which the main functions of the gas detector are initialized and verified In this phase the LEDs on the front panel are activated in sequence and the device cannot yet be used At the end of the st...

Page 11: ...onding outputs are shown in the following table Status LED Warning Fault relay Alarm relay Warm up OFF OFF Normal OFF OFF Bluetooth OFF OFF Serial connected Internal LED W8 on steady Warning delay OFF...

Page 12: ...ch function Setting mode is activated by pressing and holding the rotary switch for 5 seconds The LED that is ON acts as the menu point indicating which parameters will be set all the other LEDs are O...

Page 13: ...he operator can select the delay time for activation of the LED and the alarm relay after the alarm threshold has been exceeded See the table below for the voltage value corresponding to the selected...

Page 14: ...1 8 1800 1800 18 18 1 9 1900 1900 19 19 2 2000 2000 20 20 20 4 20 mA W 0 A 0 9600 8N2 2 1 2100 2100 21 2 2 2200 2200 22 2 3 2300 2300 23 2 4 2400 2400 24 2 5 2500 2500 25 25 2 6 2600 2600 26 2 7 2700...

Page 15: ...9700 97 9 8 9800 98 9 9 9900 99 10 10000 100 100 0 10 V W 1 A 1 4 4 Analogue output The GLACI R MIDI series gas detectors feature a single configurable analogue output During normal operation the dev...

Page 16: ...2 0 10000 ppm 1000 5000 1500 8000 ppm EC NH3 0 100 ppm 15 30 15 80 ppm 1 2 3 4 5 300 PreAlarmflag 0 300 PreAlarmflag 0 300 PreAlarmflag 0 300 PreAlarmflag 1 300 PreAlarmflag 1 307 PreWarningFlag 0 307...

Page 17: ...lly deactivated after 20 minutes of inactivity Product operation in Bluetooth mode is indicated by the rapid flashing of the green LED Bluetooth Activation is used to set up the product on installatio...

Page 18: ...LACI R app first make sure that the BLUETOOTH connection and GEOLOCATION are enabled on the smartphone used Android only Make sure that Bluetooth mode has been activated on the GLACI R MIDI using the...

Page 19: ...n access Warning ppm Threshold for activating Warning Warning Reset Determines if Warning will revert to IDLE automatically if gas levels drop below Warning threshold or requires manual acknowledgemen...

Page 20: ...relay Alarm relay Green LED Red LED Yellow LED Analogue output More screen IMPORTANT the Calibration screen is explained in detail in paragraph 5 2 CALIBRATION VIA APP Displays the app technical and l...

Page 21: ...detector Make sure that the shield is intact across the serial network Do not use the shield connection as a signal reference Use a cable that provides a dedicated wire for the signal reference Connec...

Page 22: ...dbus address Detector Modbus address Detector Modbus address 247 0 0 16 0 107 SWVer SWVer Firmware version Firmware version 6553 5 0 0 16 108 MachineCo de MachineCode MachineCod e MachineCode 6553 5 0...

Page 23: ...ess Register name Short description Medium description Long description Max value Min value Unit of meas Modbus Bit pos Modbus length Default value 300 PreAlarmFlag Alarm flag Indicator of whether the...

Page 24: ...odbus length Default value 401 ServiceDue Service needed Maintenance indicator Including calibration 1 maintenance required 1 0 0 1 0 402 Acknowledge Acknowledge Manually acknowledge warning or alarm...

Page 25: ...e sensor after approximately 7 years Calibration can be performed every 12 months if wanting to guarantee greater accuracy of the measurement or if needing to issue a new calibration certificate Below...

Page 26: ...p manual for details of all the app s features 1 2 Start calibration on the navigation bar Make sure the sensor is ready and free of gas or other sources of pollution Click Fresh air calibration at th...

Page 27: ...the room temperature and relative humidity These values will be entered on the calibration certificate to indicate the environmental conditions during calibration It is not necessary to use a calibrat...

Page 28: ...ce 2222 to register 205 Send 1 to ZeroCalibration coil 407 to perform the fresh air calibration If coil 407 is read as 0 after calibration it means that calibration was successful Send the span gas co...

Page 29: ...29 5 4 1 Diagram of the calibration procedure...

Page 30: ...30 5 4 2 Operation of the registers for calibration...

Page 31: ...J7 Close the cover Remote version Loosen the cap off the cable gland so that the cable is free to move inside the cable gland Completely unscrew the cable gland In the event of difficulties when loos...

Page 32: ...ice that detects that category of gas needs to be purchased and then the specific gas selected via app or Modbus The table in the next chapter shows the list of gases detected and the corresponding gr...

Page 33: ...000 ppm 13 R 134a 2 0 1000 ppm 2 R 22 2 0 1000 ppm 1 R 290 3 0 4000 ppm 7 R 32 1 0 1000 ppm 23 R 404A 2 0 1000 ppm 3 R 407A 1 0 1000 ppm 19 R 407C 1 0 1000 ppm 4 R 407F 1 0 1000 ppm 22 R 410A 1 0 1000...

Page 34: ...h certificate Remote cable length 5 metres Storage temperature 40 C to 50 C Storage humidity 5 90 relative humidity non condensing Storage position Any Operating temperature 40 C to 50 C Operating hum...

Page 35: ...disposed of using these services Do not hesitate to contact SAMON if you have any further questions on this topic 6 4 2 Disposal of the sensors Dispose of the sensors in accordance with local laws DA...

Page 36: ...HFC HFO Group 1 0 1000 ppm 31 220 17 GLACI R MIDI SC HFC HFO Group 2 1000 ppm SC HFC HFO Group 2 0 1000 ppm 31 520 17 GLACI R MIDI Remote SC HFC HFO Group 2 1000 ppm SC Remote HFC HFO Group 2 0 1000...

Page 37: ...0ppm SC HFC HFO Group 1 0 1000ppm SEN 42017 Sensor module SC HFC HFO Group 2 1000ppm SC HFC HFO Group 2 0 1000ppm SEN 49013 Sensor module SC R290 Group 3 4000ppm SC R290 HC 0 4000ppm SEN 45022 Sensor...

Page 38: ...38...

Page 39: ...39...

Page 40: ...40 Manufactured by Samon AB Modemgatan2 S 23539Vellinge Sweden www samon se...

Reviews: