22
4.9
Table of Modbus
®
variables
Function 04 Read Input Registers
Address Register
name
Short
description
Medium
description
Long
description
Max
value
Min
value
Unit of
meas.
Modbus
Bit pos.
Modbus
length
Default
value
101
Concentrat
ion
Concentration
ppm
Sensor
concentration
in “units”
Sensor
concentration
in “units”
6553
5
0
0
16
102
Status_0
No ICM contact No contact
with
the sensor
module
(ICM)
No contact
with the
sensor module
(ICM)
1
0
0
1
102
Status_1
No response
from the
sensor
Sensor
module
(ICM) signals
no contact
with the
sensor
Sensor
module (ICM)
signals no
contact with
the
sensor
1
0
1
1
102
Status_4
Over range
Sensor over
range
Sensor over
range
1
0
4
1
102
Status_5
Under range
Sensor under
range
Sensor under
range
1
0
5
1
103
Range
Full scale
Sensor full
scale
Sensor full
scale
6553
5
0
ppm
0
16
105
DaysOnlin
e
DaysOnline
Number of
days
online
Number of
days
online
6553
5
0
day
0
16
106
ModbusAd
dress
Modbus
address
Detector
Modbus
address
Detector
Modbus
address
247
0
0
16
0
107
SWVer
SWVer
Firmware
version
Firmware
version
6553
5
0
0
16
108
MachineCo
de
MachineCode MachineCod
e
MachineCode 6553
5
0
0
16
113
HWVer
HWVer
Hardware
version
Hardware
version
3932
1
0
0
16
114
SensorTyp
e
Sensor type
Sensor cross-
reference
table value
Sensor cross-
reference
table value
999
0
0
16
115
Units
Units
Sensor
concentration
unit
Sensor
concentration
unit
999
0
0
16
116
AnalogOut
putValue
Analogue
output
Analogue
output value
Analogue
output value
as a percent-
age
100
0
%
0
16
117
GasGroup Gas Group
Gas group
listed in the
table
1 R32
mixtures, 2
HFC/HFO, 3
HC, 4
CO2, 5 NH3
5
1
0
16
118
DaysSince
Service
Days since
service
Days since
last
service
performed
Days since last
service
performed
6553
5
0
day
0
16
119
MaxDaysO
nline
Max days
online
Maximum
number of
days online
allowed for
the sensor
Maximum
number of
days online al-
lowed for the
sensor before
replacement
is required
6553
5
0
day
0
16
120
MaxDaysT
oService
Max days to
service
Maximum
days
until next
service
Maximum days
until
next service
6553
5
0
day
0
16
365
Summary of Contents for GLACIAR MIDI
Page 1: ...GLACI R MIDI Gas Leakage Detector for commercial and industrial applications USER MANUAL...
Page 5: ...5 2 2 Physical dimensions Built in version Remote version...
Page 29: ...29 5 4 1 Diagram of the calibration procedure...
Page 30: ...30 5 4 2 Operation of the registers for calibration...
Page 38: ...38...
Page 39: ...39...
Page 40: ...40 Manufactured by Samon AB Modemgatan2 S 23539Vellinge Sweden www samon se...