IMPORTANT
The electrical connection to the bottom module is prepared for
connection to a cable of a maximum of
35 mm
2
per phase and
16 mm
2
for earth, in the event that the calculation of the cable
section required is greater.
OPTION 1
: To order special modules suitable for working at
greater consumptions.
OPTION 2
: Install the energy-saving device in such a way that
the consumption never surpasses the one corresponding to a
35 mm
2
cable section per phase and a
16 mm
2
cable section
for the earth lead.
10.1. Electrical connection between decks
If an unassembled oven is requested, it will be necessary to
carry out, further to correct piling up of the units, the bridging
of the power and control lines between the different deck that
comprise the same. In order to gain access from each deck
to the elements, where bridging is to be carried out, it will be
necessary to dismount the louvered right hand panel of each
deck; to this avail, unscrew the two hexagonal head screws
which lock it onto the back of the deck, and it will be easily
dismounted.
The oven generally comprises various superimposed decks;
bridging of switches
“R”
,
“S”
and
“T”
, (tapping of power)
is required using three copper strips (
35 mm
2
), mounted bet-
ween the inlet terminals of the respective switches.
It will also be necessary to connect between decks, and to
this until avail, simply hook up the six pole male connector of
the extreme of the regulating line of each deck, to the six pole
female connector of the installation panel of the deck which
is immediately under the same, and continue until the lower
deck where the male connector must be coupled to the female
connector located on the transformer of the base is reached.
It will not be necessary to bridge the ground terminal between
decks, as these are strongly joined together, and it will only be
necessary to joint the ground cable to the terminal indicated
on the base.
10.2. Power control connection
The power control connection between different modules is
carried out by connecting terminals
E
and
H
of the different
modules with a cable (see electrical drawing).
Summary of Contents for modular 2013
Page 31: ...Previas_Modular_13_ c f i 300413 31 salva E S P A O L...
Page 60: ...60 Previas_Modular_13_ c f i 300413 salva F R A N A I S...
Page 89: ...Previas_Modular_13_ c f i 300413 89 salva E N G L I S H...
Page 90: ...90 Previas_Modular_13_ c f i 300413 salva E N G L I S H...
Page 91: ...Previas_Modular_13_ c f i 300413 91 salva E N G L I S H...