The following are the electricity consumption related cable
sections in line with the EN 60204-1 regulation:
Consumption
Phase
section
(mm
2
)
Ground
section
(mm
2
)
<14
1.5
1.5
14
≤
A<19
2.5
2.5
19
≤
A<25
4
4
25
≤
A<32
6
6
32
≤
A<45
10
10
45
≤
A<60
16
16
60
≤
A<76
25
16
76
≤
A<94
35
16
94
≤
A<111
50
25
111
≤
A<140
70
35
140
≤
A<173
95
50
The example oven, should be connected at
400 V
by a cable
with a
25 mm
2
section (minimum) for each phase and
16mm
2
(minimum) for earth.
Modular ovens incorporate an energy-saving device which dis-
tributes power between the modules thereby reducing electri-
city consumption. Depending on configuration, a four-module
oven can be made to work with the same amount of power
required for a two or three-module oven.
If the configuration is for three modules, the total electricity
consumption will be the sum of the three most powerful mo-
dules. In these cases, the cable sections are calculated using
the new total.
For example, the total consumption of an
“E”
oven formed by
2
decks of
20 cm
1
decks of
30 cm
height with steam
Gen
1 Pizza
decks +
1 Proofer
connected at
400 V
.
Con! gured for
3 modules
Con! gured for
2 modules
Quantity
Con-
sumption
(A)
Quantity
Con-
sumption
(A)
20 cm Module
1
12.4
0
0
25 cm Module
1
15.6
1
15.6
Pizza Module
1
15.6
1
15.6
Steam Generator
1
2.0
1
2.0
Proofer
1
10
1
10
Total consump-
tion 400 V (A):
55.6
43.2
Minimum phase
cable section (mm
2
)
16
10
Minimum earth
cable section (mm
2
)
16
10
Summary of Contents for modular 2013
Page 31: ...Previas_Modular_13_ c f i 300413 31 salva E S P A O L...
Page 60: ...60 Previas_Modular_13_ c f i 300413 salva F R A N A I S...
Page 89: ...Previas_Modular_13_ c f i 300413 89 salva E N G L I S H...
Page 90: ...90 Previas_Modular_13_ c f i 300413 salva E N G L I S H...
Page 91: ...Previas_Modular_13_ c f i 300413 91 salva E N G L I S H...