English
80
Pompes Salmson 05/2015
• Fault indication: single and double pump
LC display
Setting
After another 5 seconds, the display switches to
menu level 3.
"HV" appears on the display (factory setting).
Turning the control button switches the
setting to cooling/air-conditioning (AC)
operating mode.
"AC" flashes.
The setting is applied.
The next menu is displayed.
Switching from SI to US units
"m ft" appears on the display and the currently set
unit flashes (factory setting [m]).
Turning the control button changes the
setting to [ft]. The new setting starts to
flash.
The setting is applied.
The display returns to the basic setting
.
The basic setting is displayed again if no setting is made in the menu within
30 seconds
.
LC display
Setting
If a fault occurs, the current fault is indicated by
E
= error, the
code no.
and by the motor, control
module or mains connection error source flashing.
Refer to Chapter 10 for code numbers and their
meaning.