Installation and operating instructions Siriux/Siriux-D/Siriux-O
57
English
Minimum inlet pressure (above atmospheric pressure) at the pump suction port
in order to avoid cavitation noises (at fluid temperature T
Med
):
The values apply up to 300 m above sea level; allowance for higher altitudes:
0.01 bar/100 m increase in height.
5.3 Scope of delivery
• Pump, complete
• Two flat gaskets (not for Siriux-O)
• Eight M16 washers and bolts for PN10
(for DN32-DN65 combination flanged version and DN80 flanged version)
• Installation and operating instructions
5.4 Accessoiries
Accessories must be ordered separately:
• IF Modules
• IR operating and service units (Salmson Pump Control)
See catalogue for detailed list.
6 Description and function
6.1 Description of the pump
The high-efficiency pumps Siriux are glandless pumps with a permanent magnet
rotor and an integrated differential pressure control.
The pump can be installed as
single
(Fig. 1a) or
double pump
(Fig. 1b).
1
Control module
1.1 Infrared interface
1.2 LC display
1.3 Control button
2
Direction-of-flow symbol
Nominal diameter
T
Med
T
Med
T
Med
-10°C...+50°C
+95°C
+110°C
Rp 1
0,3 bar
1,0 bar
1,6 bar
Rp 1¼
0,3 bar
1,0 bar
1,6 bar
DN 32
0,3 bar
1,0 bar
1,6 bar
DN 40 (H
max
= 4
m, 8 m, 10 m) 0,3 bar
1,0 bar
1,6 bar
DN 40 (H
max
= 12
m)
0,5 bar
1,2 bar
1,8 bar
DN 40 (H
max
= 16
m)
0,7 bar
1,5 bar
2,3 bar
DN 50 (H
max
=
8 m, 10 m)
0,3 bar
1,0 bar
1,6 bar
DN 50 (H
max
=
9
m, 12 m)
0,7 bar
1,5 bar
2,3 bar
DN 50 (H
max
= 16
m)
0,5 bar
1,2 bar
1,8 bar
DN 65 (H
max
≤
9 m)
0,5 bar
1,2 bar
1,8 bar
DN 65 (H
max
= 12
m
, 16
m)
0,7 bar
1,5 bar
2,3 bar
DN 80
0,7 bar
1,5 bar
2,3 bar