76
SALICRU
Fig. 55. AC ON-GRID connection.
8.
If you need to connect the BACK-UP output, go to the next sec-
tion. Otherwise, place the housing in its position and secure it
using the 4 screws included in the package.
9.
Insert the relevant AC circuit breakers in between, as shown
in the table below:
Model
Thermal-
magnetic
circuit
breaker
Differen-
tial relay
Over-
voltage
protec-
tion
Previous
fuse.
Max.
value (1/
phase)
EQX2 3001-HSX
2P 10 A C
curve
2P 25 A
30 mA
Class A
Type II 40
kA 230
V TT
125 A gL
EQX2 4002-HSX
2P 16 A C
curve
EQX2 5002-HSX
2P 25 A C
curve
EQX2 6002-HSX
EQX2 8002-HSX
2P 32 A C
curve
2P 32 A
30 mA
Class A
Tab. 16. AC circuit breakers.
10.
Connect the other end of the hose to the AC circuit breaker in
the junction box, downstream of the connection's IGA.
ICP
Fus.
IGA
MCB
Inverter
SPD
ID
ID
PIAs
Fig. 56. Connecting the inverter to the electrical panel.
To connect units with 24-hour monitoring, see manual
EL18700.
5.3.5.3. Steps for connecting the AC BACK-UP
connector.
1.
Remove the housing (item number 4) from its packaging.
4
2.
According to above, select an appropriate cable and pass it
through the cable gland on the housing labelled BACK-UP. A
hole must be drilled in the rubber gasket to allow the bundle to
pass, as shown in the following sequence:
BACK-UP
Cables Screw
cap
Insulation
Cover
BACK-UP
3.
Remove the insulation sleeve from the AC bundle by about
50 mm, and remove the insulation from the end of the L/N
cables by about 8 mm, as shown in Fig. 57.
Cable diameter: 12-18 mm.
8 mm.
40-60 mm.
Fig. 57. Stripping the AC cable.
4.
Remove the ferrules included in the accessory bag from the
AC BACK-UP connector and crimp them to the stripped ends
of the L/N cables with an approved tool to ensure an optimal
connection.
5.
Remove the AC BACK-UP connector from the accessory bag.
6.
Insert the ends of the three cables into the corresponding
holes on the connector: phase cable into the L port and neutral
into the N port. Make sure the cables reach the back of the
connector and screw them in tightly. Pull slightly on the cable
to check that it is properly connected.
7.
Connect the AC BACK-UP connector to the AC BACK-UP
terminal on the inverter, as shown in below: