Sunfree Series
- 17 -
4.3.2 Installation Position
Do not expose the inverter to direct solar irradiation as this could cause power
derating due to overheating. The ambient temperature should be between -25°C
~
+60°C
(
-13° F
~
140° F
)(
This temperature range is not equivalent to the
temperature range required by the battery pack
)
to ensure optimum operation.
Choose locations with sufficient air exchange. Ensure additional ventilation, when
necessary.
To make sure the installation spot is suitably ventilated, if multiple SAJ grid-tie
hybrid solar inverters are installed same area, the following safety clearance in
Figure 4.2 shall be followed for proper ventilation conditions.
50CM
30CM
50CM
30CM
30CM
Figure 4.2 Minimum Clearance