Function
Code
Function
Description
Unit
Factory
setting
Modification
Type
Communicati
on Address
frequency
type
F0.18
Acceleration
time 1
0.0s
~
6500.0s
0.1s
Due to
type
○
F012
F0.19
Deceleration
time 1
0.0s
~
6500.0s
0.1s
Due to
type
○
F013
F0.20
Default setting
0:Not restore to default
setting
1: Restore to factory
setting
2:Fault record clearing
1
0
●
F014
F2 Group
:
Motor Parameters
F2.01
Motor rate
power
0.1KW
~
400.0KW
0.1KW Due to
type
●
F201
F2.02
Motor rate
voltage
1V
~
440V
1V
Due to
type
●
F202
F2.03
Motor rate
current
0.01A
~
655.35A
(
<=55KW
)
0.1A
~
6553.5A
(
>55KW
)
0.01A/
0.1A
Due to
type
●
F203
F2.04
Motor rate
frequency
0.01Hz
~
Max
frequency
0.01Hz Due to
type
●
F204
F2.05
Motor rate
speed
1rpm
~
36000rpm
1rpm
Due to
type
●
F205
F4 Group
:
VF control
F4.00
V/F curve
setting
0:Straight line V/F
curve
2:2.0th power low torque
V/F curve
1
2
●
F400
F4.01
Torque boost 0.1%
~
30.0%
0.1%
Due to
type
○
F401
F4.02
Cut-off
frequency
0.00Hz
~
F0.10
0.01Hz 50.00Hz
○
F402
F5 Group
:
Input Terminals
F5.00
Function of
DI1
0
:
No function
1
:
Forward run
(
FWD
)
4
:
Forward JOG
(
FJOG
)
1
1
●
F500
F5.01
Function of
DI2
1
4
●
F501