GB
14
“UNITS -22°C/+5°C”
Parameter
Description
Default
min
MAX
MEASUREMENT INPUTS
/1
Room probe calibration (the parameter is expressed in eighths of degree)
+8
(eighths °C)
-40
+99
/2
evaporator probe activation (0=off;1=on)
1
0
1
/3
condenser probe activation (0=off; 1=on)
1
0
1
/6
digital input configuration (0 = open contact, 1 = closed contact)
1
0
1
/7
door open alarm delay time (0 = excluded)
120 s
0
240
/A
setpoint attivazione resistenza porta (solo se /9 = 0)
-7 °C
-40
+99
/b
door resist. activation adjustment hysteresis (only if /9 =0)
2 °C
1
15
/E
Sensor probe visualisation management (0 = normal, 1 = limited from above r0)
1
0
1
/F
defrost relay defrost management (0 = de-energized when the value set with d2 is reached on the
evaporator, 1 = de-energized at the end of time d7)
1
0
1
Pr
room probe reading
- °C
-
-
Pd
defrost/evaporator probe reading
- °C
-
-
Pc
condenser probe reading
- °C
-
-
COMPRESSOR ADJUSTMENT
r0
adjuster hysteresis (differential)
+3 °C
1
15
r1
min. operating setpoint selectable
-22 °C
-40
r2
r2
max. operating setpoint selectable
+5 °C
r1
+99
COMPRESSOR PROTECTION
C0
compressor activation delay from device start
1 min
0
240
C2
min. delay between compr. stop and subsequent start
3 min
0
240
C5
compressor start cycle time in the event of room probe alarm
10 min
1
240
C6
C5 % where compr. starts in the event of room probe alarm
70 %
0
100
DEFROST
d0
defrost interval (0= excluded)
4 hours
0
99
d1
defrost type (0= resistance, 1= hot-gas)
1
0
1
d2
end-of-defrost temp. (relating to evaporator temper.)
+12 °C
-40
+99
d3
max. defrost duration (0 = the defrosting function will not start; 255 = the defrosting function will go
on continuously)
20 min
0
255
d6
defrosting display (0=actual cell temperature, 1=stopped cell temperature, 2=dEF label)
1
0
2
d7
dripping time
4 min
0
15
dE
defrost interval count: 0= actual hours; 1=hours comp. ON; 2= autodeterm.
1
0
1
ALARMS
A0
alarm hysteresis (differential)
+2 °C
1
15
A1
min. operating setpoint alarm (0= excluded)
-2 °C
-40
0
A2
max. operating setpoint alarm (0= excluded)
+15 °C
0
+99
A3
alarm exclusion from device start
120 min
0
240
A4
buzzer activation mode for alarm : 0= always; 1= timer-controlled
1
0
1
A5
time limit for buzzer acoustic signal (only if A4 = 1)
20 s
0
240
A6
temperature alarm exclusion time (only if A1 and/or A2 0)
15 min
0
240
A7
temp. alarm exclusion time after evap. stop (for A1 and/or A2 0)
60 min
0
240
ADJUSTING THE EVAPORATOR AND CONDENSER VANS
F1
temper. above which the evap. fan stops ( only if /A = 1 and F7 = 3 or 4)
-1 °C
-40
+99
F2
fan differential (relating to F1, only if /A = 1 and F7 = 3 or 4)
+2 °C
1
15
F3
evaporator fan func. during regular operation (0=OFF; 1=ON; 2=parallel with compressor;
3=determined by F1 and F2 with comp. ON and OFF with comp. OFF
2
0
4
F4
evap. vent. operation during defrost and dripping (0= OFF, 1= ON, 2= determ. with F7)
0
0
2
F5
evaporator fan stop after dripping
3 min
0
15
F6
temperature below which the condenser fan turns off
10 °C
-40
+99
F7
condenser fan differential (relating to F6)
+3 °C
1
25
F8
condenser fan func. during regular operation (0=parallel with compr.; 1=ON); also refer to F6 and F7
0
0
1
F9
condenser fan func. during defrost and dripping (0=OFF; 1=ON, 2=ON if Tc≥26°C and OFF if
Tc<25°C)
2
0
2
FA
critical temperature for signalling high condensation temperature
46 °C
-40
+99
Fb
critical temperature for condenser dirty alarm
48 °C
-40
+99
Fc
time the condenser probe stays on the value equal or higher than FA for activation of the HtC alarm
5 min
0
240
Fd
time the condenser probe stays on the value equal or higher than Fb for activation of the dCA alarm
1 min
0
240
FE
temperature increase on the device set point value in case of an active dCA alarm
5 °C
1
15
FF
critical temperature for high pressure alarm
55 °C
-40
+99
FH
time limit used to pass from the FA value to the Fb value, within which the HP alarm is however
activated
12 s
0
15
FL
critical temperature for signalling low evaporation temperature
-37 °C
-40
+99
Summary of Contents for KP8Q
Page 10: ...IT 8 CARATTERISTICHE TECNICHE Le dimensioni degli apparecchi sono riportati di seguito 184 184...
Page 28: ......
Page 54: ......
Page 62: ...DE 8 TECHNISCHE EIGENSCHAFTEN Die Ma e der Ger te sind die folgenden 184 184...
Page 80: ......
Page 88: ...GB 8 TECHNICAL SPECIFICATIONS The dimensions of the units are found below 184 184...
Page 106: ......
Page 132: ......
Page 140: ...NL 8 TECHNISCHE KENMERKEN De apparaten hebben de volgende afmetingen 184 184...
Page 159: ...RU 1 2 2 2 3 4 8 9 10 SMART FUNCTIONS 10 11 11 11 16 17 17 21 22 22 22 22 23 23 23 24 25...
Page 160: ...RU 2 Gelateria 25 15 C HFC Z Z Y 1 2 3 4 5 N 6 B C D E F G H L R W...
Page 161: ...RU 3 OFF...
Page 162: ...RU 4 12...
Page 163: ...RU 5 A B C A B C A A A B C B C C B...
Page 164: ...RU 6 10 5 min 10 cm min 5 cm min 5 cm 4 T 30 C 55 72...
Page 165: ...RU 7 SHUKO N60320...
Page 166: ...RU 8 184 184...
Page 178: ...RU 20 22 C 5 C 25 C 15 C HtC 22 C 5 C 25 C 15 C dCA HP stand by HP 22 C 5 C 25 C 15 C LtE...
Page 180: ...RU 22 3 Sby OFF OFF...
Page 181: ...RU 23 1 2 30 OFF...
Page 182: ...RU 24 2002 96 EC 2002 96 WEEE WEEE 2002 96...
Page 192: ...P 8 CARACTER STICAS T CNICAS As dimens es dos aparelhos s o relatadas a seguir 184 184...