3.7.4
Wiring PG Speed Option Card Terminal Blocks
Use no more than 100 meters (328 feet) of wiring for PG signal lines, and keep them separate from power lines.
Use shielded, twisted-pair wires for pulse inputs and pulse output monitor wires, and connect the shield to the shield
connection terminal.
§
Wire Sizes (Same for All Models)
Terminal wire sizes are shown in
Table 3.14.
Table 3.14
Wire Sizes
Terminal
Terminal
Screws
Wire Thickness (mm
2
)
AWG Sizes
Wire Type
PG power supply
Pulse input terminal
Pulse monitor output terminal
Stranded wire: 0.5 to 1.25
Single wire:
0.5 to 1.25
20-16
Shield connection terminal
M3.5
0.5 to 2
20-14
•
Shielded, twisted-pair
wire
•
Shielded, polyethylene-
covered, vinyl sheath
cable
§
Solderless Terminals for Control Circuit Terminals
The use of solderless terminals for the control circuit terminals is recommended because solderless terminals are
easy to connect securely.
Table 3.15
Straight Solderless Terminal Sizes
Wire Thickness
(mm
2
)
AWG Sizes
Model
d1
d2
Manufacturer
0.5
20
A1 0.5-8 WH
1.00
2.60
0.75
18
A1 0.75-8 GY
1.20
2.80
1
16
A1 1-8 RD
1.40
3.00
1.5
14
A1 1.5-8 BK
1.70
3.50
Phoenix Contact
Figure 3.30
Straight Solderless Terminal Sizes
NOTE:
Do not solder wires with the control circuit terminal if wires are used instead of solderless terminals. Wires many not contact
well with the control circuit terminals or the wires may be disconnected from the control circuit terminals due to oscillation if the
wires are soldered.