background image

SAFEGREASE, SAFEOIL 
ST-1100i 
 

 

110i1CEN.doc 

16.04.2003   Rev. 1C 

12 (14) 

 

4.4.2   Lubrication cycle 

Code 

L.C.

 shows the lubrication cycle set value at display. 

Enter desired lubrication cycle value using 

Settings/Pressure

 and arrow buttons. 

The time can be set within 0 min 00 s -9999 min. In grease lubrication systems, pumping is 
started twice during one cycle. In Oil lubrication system pumping is started once during one 
cycle. 

The set value will be immediately regarded as the new lubrication cycle value and the time 
already spent in the cycle is counted as new interval time. 

4.4.3   Maximum pressurization time 

Code 

L.P.

 shows the maximum pressurization time set value at display. 

Enter desired value using 

Settings/Pressure

 and arrow buttons. 

The time can be set within 0 min 00 s -999 min. 

The center can be shut off by setting the maximum pressurization time to 0 s. The value display 
will show a phase code 

CL

. When the center is closed, only manual control operation is 

possible. 

4.4.4   Pressurization delay time coefficient 

This feature is available only in pressure switch operation. 

The value display code 

L.d.

 shows the value set for the coefficient. 

Enter the desired value using 

Settings/Pressure

 and arrow buttons. 

This value can be within the range 0.0 - 99.9. 

Delay time calculation formulas 

Formula 1. 

Delay time 

Delay time = Set maximum pressurization time * Delay time coefficient 

Formula 2. 

Delay time (max.) 

Delay time (max.) = Set lubrication cycle value/2 

 

An example: The maximum pressurization time is at 3 min. The desired delay time is 10 min. 

Set the delay time coefficient to 10min / 3 min = 3.3. 

4.4.5   Low and high pressure limits 

Low and high pressure limits are used only in pressure transmitter operation. 

The value display code 

L.o.

 tells the set value for low limit and the code 

H.i.

 tells the set value 

for high limit. 

Enter desired values using 

Settings/Pressure

 and arrow buttons. 

These limits can be set within the range of 0–160 bar (0–2320 psi.). 

Summary of Contents for ST-1100i

Page 1: ...2 Normal mode displays 5 3 1 3 Line pressure displays 6 3 1 4 Returning to normal mode 6 3 2 Extra lubrication 7 3 3 Manual control 7 3 4 Lubrication cycle counter 8 3 5 Power failure 8 3 6 Alarms 9...

Page 2: ...EASE SAFEOIL ST 1100i 110i1CEN doc 16 04 2003 Rev 1C 4 4 5 Low and high pressure limits 12 5 TECHNICAL SPECIFICATIONS 13 5 1 Technical data 13 5 2 Connections 14 5 3 Symbols 14 6 SPARE PARTS 14 2 APPE...

Page 3: ...edge of the center casing There is a green power supply LED signal pos 2 which is also the extra lubrication start button There is also a red alarm LED signal pos 3 which is also the alarm acknowledg...

Page 4: ...59 s MM SS 12 min 34 s 12 34 100 s 999 min 59 s MMM S 123 min 45 s 123 4 1000 min 999 min MMMM 1234 min 1234 9999 min 9999 12345 min 9999 2 2 3 Buttons Button Description Setting Pressure In Setting m...

Page 5: ...mit Signal is lit when the container is empty which means that the low limit switch is closed INTERLOCKING Lubrication point operation information Signal is lit when the lubrication point is not in op...

Page 6: ...lubrication system pressure switch operation pressurization Extra delay Delay time left dC Pressure discharge waiting time in pressure transmitter operation disCharge Discharge time used CL Center is...

Page 7: ...when button is pressed and vice versa when button is pressed Display codes Description HL Manual mode Hand Lubrication CC Lubrication cycle counter Cycle Counter LC Lubrication cycle set value Lubrica...

Page 8: ...n pressure transmitter operation line pressure displays can be selected with Settings Pressure button Pressing the button will show the line 1 pressure display first Another press will show line 2 pre...

Page 9: ...oil lubrication systems OS line is pressurized once Interval counter is reset when the last pressurization is started which means that the next automatic mode pressurization is performed always accor...

Page 10: ...atic mode by selecting the code OFF into the value display and by pressing Settings Pressure button after that System also returns automatically to Automatic mode if 60 minutes has gone since Manual c...

Page 11: ...n pressurization is started The same line will be pressurized again when pressure switch is open and the alarm has been acknowledged by pressing the Alarm acknowledgement button on the center cover Pr...

Page 12: ...4 1 General Center settings can be divided into two groups Set values Configuration settings Set values are lubrication system values for example lubrication cycle and maximum pressurization time Set...

Page 13: ...browsing to code PASS by means of button Display code Description C C Lubrication cycle counter Cycle Counter L C Lubrication cycle set value Lubrication Cycle L P Maximum pressurization set value Lu...

Page 14: ...isplay will show a phase code CL When the center is closed only manual control operation is possible 4 4 4 Pressurization delay time coefficient This feature is available only in pressure switch opera...

Page 15: ...the system F1 1 230 2 115 AT V AC AT V AC Power input fuse 20x5 mm glass tube fuse slow F2 5 AT Control voltage fuse 24 V for I O voltage 20x5 mm glass tube fuse slow F3 2 AT Electronic system fuse 15...

Page 16: ...V 5 A max Alarm two voltageless exchange switches loading 50V 1A max Cable channels in the casing 5 channels for 7 10 mm cable diameters 1 channel for 10 14 mm cable diameters 5 3 Symbols ST 1100i xxx...

Page 17: ......

Page 18: ......

Reviews: