CHAPTER 1 

 

- Installation 

 

Transport and handling

 

This  being  a  highly  sophisticated  electronic  unit,  it  must  be  transported  and  handled  with  care  as  per  the  precautions 
stipulated in  the foregoing section  "PRECAUTIONS". 

 

Installation

 

The installation must be carried out by responsible, competent and qualified technical personnel once the present manual 
has been fully understood. 

The  location  of  the  unit  must  meet  the  requirements  and  respect  the  precautions  stipulated  in  the  chapter 
"PRECAUTIONS", especial attention being paid to those under the heading "Most important". 

The unit must be installed in a standard single-phase installation, active phase and neutral having a difference of potential 
of 230 V AC, or a three-phase installation (3  neutral) having a difference of potential from phases to neutral of 
230 V  AC,   and  also  a  protection  conductor of  operative  earth.    Moreover,  the  installation must  have, at  its main  switch 
panel,  appropriate circuit-breakers or fuses  and a differential switch. 

Wiring 

The unit is fitted with top quality connection terminals. Each terminal has notches to enable easier fixing of the wires and 
prevent accidental removal. Likewise, the clamping screws have a self-fixing system which avoids their falling out should 
they work loose. 

Moreover, the serigraphy identifies the corresponding counter-positioned terminals on the fanning strip.  Intuitive identifying 
colours back up the graphic indications. 

1.  Connect the POWER L1 terminals to line 1 (phase 1) and POWER N to neutral of the mains line, 230V senoidal 

alternating current, 50Hz.  

2.  Connect the remaining terminals as indicated for the chosen configuration.    Please, refer to "Circuit diagrams". 

It is imperative that the wiring of the terminals and the tightening of the screws in the fanning strip be effected correctly.   

"Circuit  diagrams"  should  be  consulted.    Should  any  doubt  arise,  the  manufacturer  or  authorised  distributor  should  be 
consulted. 

 

CHAPTER 2  

- Verification and start-up 

Start-up 

Connect  all  up-stream  conductors  by  means  of  switches,  sectionalisers  or  others.  The  reinitiation  sequence  will 
automatically be carried out.  The ancillary MCB will then reset and the unit will be operative.    

Carry out all the protection tests. 

In order to carry out the protection test correctly, the unit must be  in the permanent ON position before pressing the test 
button. To this end, check that the MCB is enabled, otherwise carry out the “start-up” process. 

 

Functioning is correct when,

 once the Test button is pressed the unit cuts off and emits the corresponding diagnosis.   

When the Test has finished, the unit resets automatically in the case of  TEST OVERVOLT and LOW VOLT.  In the case of 
TEST 

I

N

 300 mA, the unit will start the countdown process for the reclosure timer. Once this process is concluded, the unit 

will reset.  Should one wish to interrupt the process,  one must press “reset”.  

Differential Test with rated threshold 

When “TEST I

N

” is pressed,  a defect current is generated in the metering toroidal of the same value as the differential 

protection, i.e. 30 mA for a 30mA RCD.  Other RCD’s, however, stick to the established legal margins and provoke a defect 
current  250 % superior to the rated value, which is no guarantee that they will actually function at the rated value.  

Such a high degree of precision and safety requires that the measurement toroidal indicate the direction in which the wiring 
be passed through This ensures that the defect intensities which circulate throughout the installation are added to the Test 
intensity rather than deducted. Therefore, when the test is carried out in an installation having zero defect intensities, one 
will have an optimum test situation.   To the contrary, should there be some defect intensity value in the installation, said 
value would be added to that of the test itself and, in such a case, the test would not be ideal.  

Autotest:  differential 

The unit automatically tests itself for differential protection every 3 seconds. It checks the constant operativity of: toroidal, 
wiring  of  same,  amplification,  filtering  and  detection.    The  performance  and  its  threshold    must  be  checked  manually     
since this involves a cut-off.   

Summary of Contents for Sureline DOV707H

Page 1: ...LED H Range 1 ...

Page 2: ...LED H Range 2 ...

Page 3: ...rising from the incorrect use of this information Safeline S L as also its affiliates is not liable to the purchaser or to third parties for damages costs etc in which the purchaser or third party may incur as a result of any accident or incorrect use of this product nor as a result of any unauthorised modification alteration or repair to same nor due to non observance of the operation and mainten...

Page 4: ...ls relay OUT and remote IN 6 Version number of sequential reclosures of differential and MCB AIT EAI VOD ERT ETE RET TEL 7 Protection delay No suffix rapid version standard M medium version S slow version 8 Sensitivity differential intensity 30mA I n 30mA 300mA I n 300mA standard Sin sufijo in models without differential intensity OVD706H 9 Power supply Line Neutral No suffix Not designed to allow...

Page 5: ...nd transient overvoltage 13 Protection against permanent and transient low voltage 14 Protection against tripping of MCB 14 Protection against untimely tripping of the differential 14 CHAPTER 4 Cut off Tripping times Total cut off time of the MCB 14 CHAPTER 5 Mode of Use Remote Control 14 CHAPTER 6 Description of basic components Toroidal differential intensity transformer TRDF18 15 Toroidal diffe...

Page 6: ...o 9ms typical 2 pole consult Cut off Tripping times Delay REMOTE IN 3 ms Mechanical endurance Safeline reclosure module 100 000 complete manoeuvres ON OFF Mechanical endurance Schupa MCB 20 000 complete manoeuvres ON OFF Mechanical endurance General Electric MCB 2 pole 20 000 complete manoeuvres ON OFF Mechanical endurance General Electric MCB 4 pole 15 000 complete manoeuvres ON OFF Typical preci...

Page 7: ...nt reclosure Static Green LED WORKING and Red LED s LOW VOLT I n OVERVOLT in periodic 3 second sequence autotest 3 Static Red LED s anomaly Static Red LED I N 300 mA or 30 mA acc version anomaly in the differential Due to error in the toroidal core wiring or differential circuit Static Red LED LOW VOLT anomaly in the input mains voltage Due to abnormally low voltage inferior to 150 V AC approx Oth...

Page 8: ...1 N POWER 230V SUPPLY NEUTRAL INPUT METERING SENSOR INPUT N L2 INPUT 2 INPUT METERING SENSOR L2 LINE 2 230V N INPUT 2 INPUT METERING SENSOR N NEUTRAL L3 INPUT 3 INPUT METERING SENSOR L3 LINE 3 230V N INPUT 3 INPUT METERING SENSOR N NEUTRAL Description of module s front connection terminals R type terminals I SENSOR 1 INPUT 1 DIFFERENTIAL INTENSITY SENSOR G SENSOR 1 COMMON 1 SENSOR AND TEST T SENSO...

Page 9: ... terminals U type terminals Automatic Sequential Resets RCD and MCB Nbr of automatic sequential reclosures differential I n Ten 3 3 3 3 3 3 3 3 3 and 3 mins Model suffix ETE RET TEL Nbr of automatic sequential reclosures MCB Two 3 and 3 mins Model suffix ETE RET TEL Reset to zero reclosure counter 30 mins Model suffix ETE RET TEL Nbr of automatic sequential reclosures differential I n Six 3 6 12 3...

Page 10: ...closure due to overvoltage Low voltage protection Line1 Line2 Line3 Line1 Line1 Automatic intelligent reclosure due to low voltage Line1 Line1 Protection differential intensity I n 30 mA or 300 mA acc version Automatic sequential reclosure differential protection I n MCB protection 10kA 15kA acc version EN 60947 2 Automatic sequential reclosure MCB protection Overvoltage test Low voltage test Rate...

Page 11: ...nical service must be contacted immediately in order for the unit to be examined The unit must be completely disconnected from the mains before cleaning This is to be effected with a soft dry brush and if need be with a slightly damp cloth The unit must not be reconnected to the mains until having ascertained that it is completely dry WARNING This unit must be installed in a standard enclosure the...

Page 12: ...t up Start up Connect all up stream conductors by means of switches sectionalisers or others The reinitiation sequence will automatically be carried out The ancillary MCB will then reset and the unit will be operative Carry out all the protection tests In order to carry out the protection test correctly the unit must be in the permanent ON position before pressing the test button To this end check...

Page 13: ...no difference in intensity between phase and neutral In this case the differential protections do not act but then neither would any receiver being supplied from phase to neutral The functioning of the protection devices against defect currents which derive or leak to earth differentials is based on the measurement of the difference in intensity between the live conductors phase and neutral Once t...

Page 14: ...aving read and fully understood the present manual and having started up the unit the user may then proceed to connect up the elements of consumption to the protected line and the unit will operate as described in CHAPTERS 2 and 3 Before using the unit the complete Protection Test must be carried out If the unit is to be put to permanent use testing must be done as a matter of routine Once the tes...

Page 15: ...ype EP 100 Breaking capacity 15KA IEC 60947 2 ó 10KA IEC 60898 Curve C standard D B K Intensities 6 10 16 25 32 40 50 63 A Mechanical endurance MCB 2P and 4P 20 000 Complete manoeuvres ON OFF For further information please consult the manufacturer Very high speed disconnector tripping coil Manufacturer General Electric Type TELE L 1 CA 24 60V For further information please consult the manufacturer...

Page 16: ...xternal MCB and accessories CHAPTER 9 Additional options The new range of protection metering and registering share the SURELINE philosophy and are extraordinarily versatile So much so that they permit multiple configurations thanks to their modular expansion architecture not only with present and future SURELINE elements but also with others available on the market Thus they complement and are co...

Page 17: ...t for its repair or servicing Cost of all components replacements and labour on original components The guarantee does NOT cover Transport Breakdown caused by non original components or devices Defects caused by incorrect installation Damage caused by incorrect usage or errors arising from repairs and internal manipulation by unauthorised persons Consumables fuses thermal fuses varistors and labou...

Page 18: ...inst any defect of manufacture or original components as determined by our Technical Service Any repair or substitution does not extend the guarantee period The guarantee covers Reception of the unit for its repair or servicing Cost of all components replacements and labour on original components The guarantee does NOT cover Transport Breakdown caused by non original components or devices Defects ...

Page 19: ...ORNAS TIPO U A B N L1 CONTROL OUT INPUT 1 POWER 230V SENSOR 1 I G T 1 2 3 4 AUXILIARY IN OUT CONSULT MANUAL 5 6 7 8 COM L1 L2 9 M Self Reclosing DOV 707H Consult Manual Protection Unit 300 mA O VERVO LT TEST LOW VOLT LO W VO LT I N I 300 m A N Reclosure WORKING TIM ER ON OFF TEST I N BLOCK RESET TEST OVER VOLT BORNA BORNAS NO CONECTAR VERSION BORNAS TIPO U BORNA BORNAS AUXILIARY IN OUT CONTACTO N ...

Page 20: ...X I G T 1 2 SENSO R 1 M Self Reclosing DOV 707H Consult Manual Protection Unit 300 mA O VERVO LT TEST LOW VOLT LO W VO LT I N I 300 m A N Reclosure WORKING TIM ER ON OFF TEST I N BLOCK RESET TEST OVER VOLT T G I CAUTION POSITION TRDF18 CONSULT MANUAL CONFIGURACION MONOFASICA 2 POLOS 6 10 16 20 25 32 40 50 Y 63A UNIDAD DE PROTECCION AUTORREARMABLE CON MOTOR REARMADOR INTEGRADO MODELOS DOV707H Y DOV...

Page 21: ...ARMADOR INTEGRADO MODELOS DOV707HT Y DOV107HT VERSION BORNAS TIPO U BORNA BORNAS NO CONECTAR VERSION BORNAS TIPO U BORNA BORNAS AUXILIARY IN OUT CONTACTO N O RELE CONTACTO N C RELE Nº RELE DE SALIDA 5A MAX AC1 4 2 3 RELE DE SALIDA CONMUTADO LIBRE DE POTECIAL CON FUNCION DE DESCONEXION DESBLOQUEO BORNA BORNAS AUXILIARY IN OUT ENTRADA REMOTE IN ENTRADA REMOTE IN Nº ENTRADAS REMOTE IN 8 9 ENTRADAS PA...

Page 22: ...N SENTIDO FLECHA TRDF18 ó TRDF26 PASAR LOS CONDUCTORES L1 L2 L3 Y NEUTRO T G I CAUTION POSITION TRDF18 CONSULT MANUAL UNIDAD DE PROTECCION AUTORREARMABLE CON MOTOR REARMADOR INTEGRADO MODELOS DOV707HT Y DOV107HT VERSION BORNAS TIPO R BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR BLOQUEO 1 2 RELE BORNA...

Page 23: ...R 1 I G T 1 2 3 4 AUXILIARY IN OUT CON SULT MANUAL 5 6 7 8 COM L1 L2 9 M Self Reclosing OVD 706H Consult Manual Protection Unit O VERVO LT TEST LOW VOLT LO W VO LT BLO CK Reclosure WORKING TIM ER RESET TEST OVER VOLT 1 2 3 ON OFF BORNA BORNAS AUXILIARY IN OUT CONTACTO N O RELE CONTACTO N C RELE Nº RELE DE SALIDA 5A MAX AC1 4 2 3 RELE DE SALIDA CONMUTADO LIBRE DE POTECIAL CON FUNCION DE DESCONEXION...

Page 24: ...BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR ALARMA Y BLOQUEO BORNA BORNA NO CONECTAR BORNA NO CONECTAR BORNA NO CONECTAR BORNAS NO CONECTAR I 1 2 RELE T G A B N L1 CONTROL OUT INPUT 1 POWER 230V AUX I G T 1 2 SENSOR 1 M Self Reclosing OVD 706H Consult Manual Protection Unit O VERVO LT TEST LOW VOLT ...

Page 25: ... BORNA BORNAS AUXILIARY IN OUT ENTRADA REMOTE IN ENTRADA REMOTE IN Nº ENTRADAS REMOTE IN 8 9 ENTRADAS PARA CONTACTO EXTERNO LIBRE DE POTENCIAL RELE 3 4 2 CON FUNCION DE ACTIVACION POR ALARMA Y BLOQUEO CONTACTO COMUN RELE Y PUESTA A CERO DE LA CUENTA DE DISPAROS 6 1 5 7 BORNA NO CONECTAR BORNA NO CONECTAR BORNA NO CONECTAR BORNA NO CONECTAR SENSOR 1 I G T 1 2 3 4 AUXILIARY IN OUT CONSULT MANUAL 5 6...

Page 26: ...tection Unit O VERVO LT TEST VOLT OVER LO W VO LT BLO CK Reclosure ON OFF RESET TIM ER L3 L2 TEST VOLT LOW L1 WORKING 1 2 3 BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR ALARMA Y BLOQUEO BORNA BORNA NO CONECTAR BORNA NO CONECTAR BORNA NO CONECTAR BORNAS NO CONECTAR I 1 2 RELE T G BORNA Nº 2 Y 3 CONTAC...

Page 27: ...BORNAS TIPO U BORNA BORNAS AUXILIARY IN OUT CONTACTO N O RELE CONTACTO N C RELE Nº RELE DE SALIDA 5A MAX AC1 4 2 3 RELE DE SALIDA CONMUTADO LIBRE DE POTECIAL CON FUNCION DE DESCONEXION DESBLOQUEO BORNA BORNAS AUXILIARY IN OUT ENTRADA REMOTE IN ENTRADA REMOTE IN Nº ENTRADAS REMOTE IN 8 9 ENTRADAS PARA CONTACTO EXTERNO LIBRE DE POTENCIAL RELE 3 4 2 CON FUNCION DE ACTIVACION POR ALARMA Y BLOQUEO CONT...

Page 28: ...LT MANUAL CONFIGURACION MONOFASICA 2 POLOS 6 10 16 20 25 32 40 50 Y 63A UNIDAD DE PROTECCION AUTORREARMABLE CON MOTOR REARMADOR INTEGRADO MODELOS RDI705H Y RDI105H VERSION BORNAS TIPO R BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR BLOQUEO 1 2 RELE BORNA Nº 2 Y 3 CONTACTO AUX ILIAR NORMALMENTE CERRADO...

Page 29: ...RMABLE CON MOTOR REARMADOR INTEGRADO BORNA BORNAS NO CONECTAR VERSION BORNAS TIPO U BORNA BORNAS AUXILIARY IN OUT CONTACTO N O RELE CONTACTO N C RELE Nº RELE DE SALIDA 5A MAX AC1 4 2 3 RELE DE SALIDA CONMUTADO LIBRE DE POTECIAL CON FUNCION DE DESCONEXION DESBLOQUEO BORNA BORNAS AUXILIARY IN OUT ENTRADA REMOTE IN ENTRADA REMOTE IN Nº ENTRADAS REMOTE IN 8 9 ENTRADAS PARA CONTACTO EXTERNO LIBRE DE PO...

Page 30: ... Y POSICIONARLO SEGUN SENTIDO FLECHA TRDF18 ó TRDF26 PASAR LOS CONDUCTORES L1 L2 L3 Y NEUTRO T G I CAUTION POSITION TRDF18 CONSULT MANUAL UNIDAD DE PROTECCION AUTORREARMABLE CON MOTOR REARMADOR INTEGRADO MODELOS RDI705HT Y RDI105HT VERSION BORNAS TIPO R BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR BL...

Page 31: ...H Range 31 DIMENSIONES TRANSFORMADORES TOROIDALES TRDF18 TRIT18 70 80 Ø 18 10 50 14 50 50 52 60 30 70 DIMENSIONES TRANSFORMADORES TOROIDALES TRDF26 TRIT26 Ø 26 10 50 14 70 76 30 30 90 40 76 Ø 4 20 30 10 80 ...

Page 32: ...302 MATARO Barcelona SPAIN www safeline es safeline safeline es R D Commercial Factory Administration T 34 93 8841820 T 34 93 7630801 T 34 93 7630671 T 34 93 8841821 F 34 93 7630090 F 34 93 7630090 comercial safeline es inves safeline es admin safeline es Made in EU ...

Reviews: