PRECAUTIONS / WARNINGS FOR USER / INSTALLER: 

  Despite this unit's being of maximum safety, both from a design and features standpoint, the utmost care must always 

be taken when using it. It must not be used until its characteristics and mode of operation have been fully understood. 

  Generally  speaking,  the  precautions  to  be  taken  with  this  unit  do  not  differ  from  those  taken  with  any  other  piece  of 

electronic equipment connected to the mains.  Nevertheless, special attention should be paid to the following: 

  It must be borne in mind that the unit resets the ancillary circuit-breaker automatically  and this fact could cause injury to 

a careless operator or user.  In order to avoid this: 

  all up-stream conductors are to be disconnected. (by means of switches, sectionalisers or others.) 

  The  mission  of the ancillary circuit-breaker element is not that of protecting the circuit-breaker, but rather that of acting 

as merely as an ancillary switch.   The installation should, therefore, be equipped with elements of protection against 
over-intensity  (i.e.  circuit-breakers,  fuses,  etc...)  The  wiring  of  the  installation  must  be  foreseen  for  the  maximum 
intensity of the protection elements. 

  Do not apply current nor use the module until it has been correctly installed in a standard enclosure. 

  Do not connect the unit up to voltages other than  230 V AC ± 25%. 

  Do not connect up to installations which may supply intensities of over 15 kA or 10 kA (depending on ancillary MCB) 

  When power supply to the unit is cut off or below minimum (150V AC approx.), o total reset to zero of counters, timers 

and conditions is generated. 

  Terminals A and B of "CONTROL OUT" must not be short-circuited under any circumstance whatsoever. Should this 

occur, irreversible damage would be caused to the protection module. 

  Caution: The unit’s connecting terminals are not insulated from the mains 

  Do not expose to liquids or humidity. 

  Do not drop, knock or expose to vibrations.. 

  Do not expose to sources of heat 

  Do not expose to environmental temperatures below 0

o

, -15

o

 C. Or over 40

o

, 50

o

, 70

o

 C (depending on version). 

  Do not expose to magnetic sources or emissions (electric motors and transformers, electro-magnets, etc.). 

  Under  no  circumstance  whatsoever  must  the  unit  be  opened  and  the  interior  manipulated.    The  safety  seals  must 

remain intact.  Should they be broken, the correct functioning of the unit could be jeopardised. 

  In the event of any of the above occurring, the authorised technical service must be contacted immediately in order for 

the unit to be examined. 

  The unit must be completely disconnected from the mains before cleaning.  This is to be effected with a soft, dry brush 

and, if need be, with a slightly damp cloth.  The unit must not be reconnected to the mains until having ascertained that 
it is completely dry.

 

WARNING!

 

 

  This  unit  must  be  installed  in  a  standard  enclosure,  the  only  part  within  access  of  the  user  being  the  display  and 

command panel.  Its application is restricted to industrial installations. 

 

Most  important

 

 

Positioning of the toroidal transformer and individualized adjustment to its module

 

The  differential  intensity  toroidal  core  is  individually  matched  and  adjusted  to  the  corresponding  Sureline  module. 
Therefore,  these  elements  can,  under  no  circumstance  whatsoever,  be  interchanged  with  others  bearing  the  same 
reference and from other Sureline modules.  Were this toroidal core to be interchanged, the measurement obtained for 
the differential protection would be erroneous and operation would be abnormal.  Only the toroidal transformers supplied 
for the specific Sureline module can be installed.  Each toroidal core indicates the model and serial number of the Sureline 
module for which it has been specifically matched and adjusted.  The toroidal transformer must of necessity be positioned

 

as  shown  in  the  “Wiring  diagrams”,  the  direction  of  the  arrow  indicating  the  position  with  respect  to  the  wiring.    The 
length of the wire connecting the toroidal core to the SURELINE unit must not exceed 30 cms. 

- Wiring 

It is of  the utmost importance that 

the correct polarity is ensured upon connection of the SURELINE “L1” and “N” 

terminals. 

If  this  polarity  is  not  respected,  the  high  accuracy  is  lost  originating  errors  in  measurement  and  abnormal 

functioning of the protections.  

A main risk of the unit not functioning correctly could be originated principally by an incorrect wiring up of the connection 
terminals.    It  is,  therefore,  of  the  utmost  importance

  that  this  wiring  be  carried  out  correctly 

in  accordance  with  the 

following protocol: 

 

a homologated "male pin" is to be incorporated in the naked core of the stripped pliable conductor. 

 

these terminals are placed in the corresponding grooves as far in as they will go 

 

ensure that the conductor lead is correctly fixed with the pertinent  tightening torque, i.e. there must be no 
displacement of the terminal nor any damage to the screws on head, thread, fillet or washer, any of which 
would be to the subsequent detriment of the assemblies and screw connections. 

The user must carry out the complete protection test periodically as is described in CHAPTER 2. 

Summary of Contents for Sureline DOV707H

Page 1: ...LED H Range 1 ...

Page 2: ...LED H Range 2 ...

Page 3: ...rising from the incorrect use of this information Safeline S L as also its affiliates is not liable to the purchaser or to third parties for damages costs etc in which the purchaser or third party may incur as a result of any accident or incorrect use of this product nor as a result of any unauthorised modification alteration or repair to same nor due to non observance of the operation and mainten...

Page 4: ...ls relay OUT and remote IN 6 Version number of sequential reclosures of differential and MCB AIT EAI VOD ERT ETE RET TEL 7 Protection delay No suffix rapid version standard M medium version S slow version 8 Sensitivity differential intensity 30mA I n 30mA 300mA I n 300mA standard Sin sufijo in models without differential intensity OVD706H 9 Power supply Line Neutral No suffix Not designed to allow...

Page 5: ...nd transient overvoltage 13 Protection against permanent and transient low voltage 14 Protection against tripping of MCB 14 Protection against untimely tripping of the differential 14 CHAPTER 4 Cut off Tripping times Total cut off time of the MCB 14 CHAPTER 5 Mode of Use Remote Control 14 CHAPTER 6 Description of basic components Toroidal differential intensity transformer TRDF18 15 Toroidal diffe...

Page 6: ...o 9ms typical 2 pole consult Cut off Tripping times Delay REMOTE IN 3 ms Mechanical endurance Safeline reclosure module 100 000 complete manoeuvres ON OFF Mechanical endurance Schupa MCB 20 000 complete manoeuvres ON OFF Mechanical endurance General Electric MCB 2 pole 20 000 complete manoeuvres ON OFF Mechanical endurance General Electric MCB 4 pole 15 000 complete manoeuvres ON OFF Typical preci...

Page 7: ...nt reclosure Static Green LED WORKING and Red LED s LOW VOLT I n OVERVOLT in periodic 3 second sequence autotest 3 Static Red LED s anomaly Static Red LED I N 300 mA or 30 mA acc version anomaly in the differential Due to error in the toroidal core wiring or differential circuit Static Red LED LOW VOLT anomaly in the input mains voltage Due to abnormally low voltage inferior to 150 V AC approx Oth...

Page 8: ...1 N POWER 230V SUPPLY NEUTRAL INPUT METERING SENSOR INPUT N L2 INPUT 2 INPUT METERING SENSOR L2 LINE 2 230V N INPUT 2 INPUT METERING SENSOR N NEUTRAL L3 INPUT 3 INPUT METERING SENSOR L3 LINE 3 230V N INPUT 3 INPUT METERING SENSOR N NEUTRAL Description of module s front connection terminals R type terminals I SENSOR 1 INPUT 1 DIFFERENTIAL INTENSITY SENSOR G SENSOR 1 COMMON 1 SENSOR AND TEST T SENSO...

Page 9: ... terminals U type terminals Automatic Sequential Resets RCD and MCB Nbr of automatic sequential reclosures differential I n Ten 3 3 3 3 3 3 3 3 3 and 3 mins Model suffix ETE RET TEL Nbr of automatic sequential reclosures MCB Two 3 and 3 mins Model suffix ETE RET TEL Reset to zero reclosure counter 30 mins Model suffix ETE RET TEL Nbr of automatic sequential reclosures differential I n Six 3 6 12 3...

Page 10: ...closure due to overvoltage Low voltage protection Line1 Line2 Line3 Line1 Line1 Automatic intelligent reclosure due to low voltage Line1 Line1 Protection differential intensity I n 30 mA or 300 mA acc version Automatic sequential reclosure differential protection I n MCB protection 10kA 15kA acc version EN 60947 2 Automatic sequential reclosure MCB protection Overvoltage test Low voltage test Rate...

Page 11: ...nical service must be contacted immediately in order for the unit to be examined The unit must be completely disconnected from the mains before cleaning This is to be effected with a soft dry brush and if need be with a slightly damp cloth The unit must not be reconnected to the mains until having ascertained that it is completely dry WARNING This unit must be installed in a standard enclosure the...

Page 12: ...t up Start up Connect all up stream conductors by means of switches sectionalisers or others The reinitiation sequence will automatically be carried out The ancillary MCB will then reset and the unit will be operative Carry out all the protection tests In order to carry out the protection test correctly the unit must be in the permanent ON position before pressing the test button To this end check...

Page 13: ...no difference in intensity between phase and neutral In this case the differential protections do not act but then neither would any receiver being supplied from phase to neutral The functioning of the protection devices against defect currents which derive or leak to earth differentials is based on the measurement of the difference in intensity between the live conductors phase and neutral Once t...

Page 14: ...aving read and fully understood the present manual and having started up the unit the user may then proceed to connect up the elements of consumption to the protected line and the unit will operate as described in CHAPTERS 2 and 3 Before using the unit the complete Protection Test must be carried out If the unit is to be put to permanent use testing must be done as a matter of routine Once the tes...

Page 15: ...ype EP 100 Breaking capacity 15KA IEC 60947 2 ó 10KA IEC 60898 Curve C standard D B K Intensities 6 10 16 25 32 40 50 63 A Mechanical endurance MCB 2P and 4P 20 000 Complete manoeuvres ON OFF For further information please consult the manufacturer Very high speed disconnector tripping coil Manufacturer General Electric Type TELE L 1 CA 24 60V For further information please consult the manufacturer...

Page 16: ...xternal MCB and accessories CHAPTER 9 Additional options The new range of protection metering and registering share the SURELINE philosophy and are extraordinarily versatile So much so that they permit multiple configurations thanks to their modular expansion architecture not only with present and future SURELINE elements but also with others available on the market Thus they complement and are co...

Page 17: ...t for its repair or servicing Cost of all components replacements and labour on original components The guarantee does NOT cover Transport Breakdown caused by non original components or devices Defects caused by incorrect installation Damage caused by incorrect usage or errors arising from repairs and internal manipulation by unauthorised persons Consumables fuses thermal fuses varistors and labou...

Page 18: ...inst any defect of manufacture or original components as determined by our Technical Service Any repair or substitution does not extend the guarantee period The guarantee covers Reception of the unit for its repair or servicing Cost of all components replacements and labour on original components The guarantee does NOT cover Transport Breakdown caused by non original components or devices Defects ...

Page 19: ...ORNAS TIPO U A B N L1 CONTROL OUT INPUT 1 POWER 230V SENSOR 1 I G T 1 2 3 4 AUXILIARY IN OUT CONSULT MANUAL 5 6 7 8 COM L1 L2 9 M Self Reclosing DOV 707H Consult Manual Protection Unit 300 mA O VERVO LT TEST LOW VOLT LO W VO LT I N I 300 m A N Reclosure WORKING TIM ER ON OFF TEST I N BLOCK RESET TEST OVER VOLT BORNA BORNAS NO CONECTAR VERSION BORNAS TIPO U BORNA BORNAS AUXILIARY IN OUT CONTACTO N ...

Page 20: ...X I G T 1 2 SENSO R 1 M Self Reclosing DOV 707H Consult Manual Protection Unit 300 mA O VERVO LT TEST LOW VOLT LO W VO LT I N I 300 m A N Reclosure WORKING TIM ER ON OFF TEST I N BLOCK RESET TEST OVER VOLT T G I CAUTION POSITION TRDF18 CONSULT MANUAL CONFIGURACION MONOFASICA 2 POLOS 6 10 16 20 25 32 40 50 Y 63A UNIDAD DE PROTECCION AUTORREARMABLE CON MOTOR REARMADOR INTEGRADO MODELOS DOV707H Y DOV...

Page 21: ...ARMADOR INTEGRADO MODELOS DOV707HT Y DOV107HT VERSION BORNAS TIPO U BORNA BORNAS NO CONECTAR VERSION BORNAS TIPO U BORNA BORNAS AUXILIARY IN OUT CONTACTO N O RELE CONTACTO N C RELE Nº RELE DE SALIDA 5A MAX AC1 4 2 3 RELE DE SALIDA CONMUTADO LIBRE DE POTECIAL CON FUNCION DE DESCONEXION DESBLOQUEO BORNA BORNAS AUXILIARY IN OUT ENTRADA REMOTE IN ENTRADA REMOTE IN Nº ENTRADAS REMOTE IN 8 9 ENTRADAS PA...

Page 22: ...N SENTIDO FLECHA TRDF18 ó TRDF26 PASAR LOS CONDUCTORES L1 L2 L3 Y NEUTRO T G I CAUTION POSITION TRDF18 CONSULT MANUAL UNIDAD DE PROTECCION AUTORREARMABLE CON MOTOR REARMADOR INTEGRADO MODELOS DOV707HT Y DOV107HT VERSION BORNAS TIPO R BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR BLOQUEO 1 2 RELE BORNA...

Page 23: ...R 1 I G T 1 2 3 4 AUXILIARY IN OUT CON SULT MANUAL 5 6 7 8 COM L1 L2 9 M Self Reclosing OVD 706H Consult Manual Protection Unit O VERVO LT TEST LOW VOLT LO W VO LT BLO CK Reclosure WORKING TIM ER RESET TEST OVER VOLT 1 2 3 ON OFF BORNA BORNAS AUXILIARY IN OUT CONTACTO N O RELE CONTACTO N C RELE Nº RELE DE SALIDA 5A MAX AC1 4 2 3 RELE DE SALIDA CONMUTADO LIBRE DE POTECIAL CON FUNCION DE DESCONEXION...

Page 24: ...BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR ALARMA Y BLOQUEO BORNA BORNA NO CONECTAR BORNA NO CONECTAR BORNA NO CONECTAR BORNAS NO CONECTAR I 1 2 RELE T G A B N L1 CONTROL OUT INPUT 1 POWER 230V AUX I G T 1 2 SENSOR 1 M Self Reclosing OVD 706H Consult Manual Protection Unit O VERVO LT TEST LOW VOLT ...

Page 25: ... BORNA BORNAS AUXILIARY IN OUT ENTRADA REMOTE IN ENTRADA REMOTE IN Nº ENTRADAS REMOTE IN 8 9 ENTRADAS PARA CONTACTO EXTERNO LIBRE DE POTENCIAL RELE 3 4 2 CON FUNCION DE ACTIVACION POR ALARMA Y BLOQUEO CONTACTO COMUN RELE Y PUESTA A CERO DE LA CUENTA DE DISPAROS 6 1 5 7 BORNA NO CONECTAR BORNA NO CONECTAR BORNA NO CONECTAR BORNA NO CONECTAR SENSOR 1 I G T 1 2 3 4 AUXILIARY IN OUT CONSULT MANUAL 5 6...

Page 26: ...tection Unit O VERVO LT TEST VOLT OVER LO W VO LT BLO CK Reclosure ON OFF RESET TIM ER L3 L2 TEST VOLT LOW L1 WORKING 1 2 3 BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR ALARMA Y BLOQUEO BORNA BORNA NO CONECTAR BORNA NO CONECTAR BORNA NO CONECTAR BORNAS NO CONECTAR I 1 2 RELE T G BORNA Nº 2 Y 3 CONTAC...

Page 27: ...BORNAS TIPO U BORNA BORNAS AUXILIARY IN OUT CONTACTO N O RELE CONTACTO N C RELE Nº RELE DE SALIDA 5A MAX AC1 4 2 3 RELE DE SALIDA CONMUTADO LIBRE DE POTECIAL CON FUNCION DE DESCONEXION DESBLOQUEO BORNA BORNAS AUXILIARY IN OUT ENTRADA REMOTE IN ENTRADA REMOTE IN Nº ENTRADAS REMOTE IN 8 9 ENTRADAS PARA CONTACTO EXTERNO LIBRE DE POTENCIAL RELE 3 4 2 CON FUNCION DE ACTIVACION POR ALARMA Y BLOQUEO CONT...

Page 28: ...LT MANUAL CONFIGURACION MONOFASICA 2 POLOS 6 10 16 20 25 32 40 50 Y 63A UNIDAD DE PROTECCION AUTORREARMABLE CON MOTOR REARMADOR INTEGRADO MODELOS RDI705H Y RDI105H VERSION BORNAS TIPO R BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR BLOQUEO 1 2 RELE BORNA Nº 2 Y 3 CONTACTO AUX ILIAR NORMALMENTE CERRADO...

Page 29: ...RMABLE CON MOTOR REARMADOR INTEGRADO BORNA BORNAS NO CONECTAR VERSION BORNAS TIPO U BORNA BORNAS AUXILIARY IN OUT CONTACTO N O RELE CONTACTO N C RELE Nº RELE DE SALIDA 5A MAX AC1 4 2 3 RELE DE SALIDA CONMUTADO LIBRE DE POTECIAL CON FUNCION DE DESCONEXION DESBLOQUEO BORNA BORNAS AUXILIARY IN OUT ENTRADA REMOTE IN ENTRADA REMOTE IN Nº ENTRADAS REMOTE IN 8 9 ENTRADAS PARA CONTACTO EXTERNO LIBRE DE PO...

Page 30: ... Y POSICIONARLO SEGUN SENTIDO FLECHA TRDF18 ó TRDF26 PASAR LOS CONDUCTORES L1 L2 L3 Y NEUTRO T G I CAUTION POSITION TRDF18 CONSULT MANUAL UNIDAD DE PROTECCION AUTORREARMABLE CON MOTOR REARMADOR INTEGRADO MODELOS RDI705HT Y RDI105HT VERSION BORNAS TIPO R BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR BL...

Page 31: ...H Range 31 DIMENSIONES TRANSFORMADORES TOROIDALES TRDF18 TRIT18 70 80 Ø 18 10 50 14 50 50 52 60 30 70 DIMENSIONES TRANSFORMADORES TOROIDALES TRDF26 TRIT26 Ø 26 10 50 14 70 76 30 30 90 40 76 Ø 4 20 30 10 80 ...

Page 32: ...302 MATARO Barcelona SPAIN www safeline es safeline safeline es R D Commercial Factory Administration T 34 93 8841820 T 34 93 7630801 T 34 93 7630671 T 34 93 8841821 F 34 93 7630090 F 34 93 7630090 comercial safeline es inves safeline es admin safeline es Made in EU ...

Reviews: