LED (H) Range
8
Description of display panel RDI705H - RDI705HT - RDI705HL - RDI705HLT- RDI705HLL - RDI705HLLT
1- Square yellow pushbuttons: vary depending on context:
TEST LOW VOLT
TEST
I
N
TEST
I
N
+ TEST LOW VOLT = reset
2 – LED’s vary depending on context:
Static Green LED (WORKING) : unit is in metering process
Blinking Red LED (TIMER Reclosure) : countdown in process and when this finishes unit will reclose
Blinking Red LED
I
N
300 mA or 30 mA (acc. version): cut-off due to differential intensity
Blinking Red LED (LOW VOLT) : cut-off due to low voltage of module’s line supply (double blinking : permanent low voltage).
Blinking Red LED (BLOCK) : unit blocked due to sequential reclosures used up.
Red LED’s (LOW VOLT, I
n, BLOCK, TIMER) in periodic to-fro sequence : imminent reclosure
Static Green LED (WORKING) and Red LED’s (LOW VOLT, I
n, BLOCK) in periodic 3-second sequence : autotest.
3 – Static Red LED’s : anomaly
Static Red LED
I
N
300 mA or 30 mA (acc. version): anomaly in the differential.
Due to error in the toroidal core, wiring or differential circuit.
Static Red LED (LOW VOLT) : anomaly in the input mains voltage.
Due to abnormally low voltage,
inferior to 150 V AC. approx.
Other Static Red LED’s : anomaly. Do not use unit. Consult technical service.
4 – Sliding ON/OFF switch:
ON: normal functioning
OFF: disconnection and totally blocked
ON + RESET: to start up
- Description of module’s connection terminals at rear
A CONTROL OUT
OUTPUT VERY HIGH SPEED TRIPPING COIL TERMINAL A
B CONTROL OUT
OUTPUT VERY HIGH SPEED TRIPPING COIL TERMINAL B
L1 POWER 230V SUPPLY: PHASE (LINE) 230V + INPUT METERING SENSOR INPUT L1
N POWER 230V SUPPLY: N INPUT METERING SENSOR INPUT N
L2 INPUT 2
INPUT METERING SENSOR L2 (LINE 2) 230V
N INPUT 2
INPUT METERING SENSOR N (NEUTRAL)
L3 INPUT 3
INPUT METERING SENSOR L3 (LINE 3) 230V
N INPUT 3
INPUT METERING SENSOR N (NEUTRAL)
- Description of module’s front connection terminals (R-type terminals)
I SENSOR 1
INPUT 1 DIFFERENTIAL INTENSITY SENSOR
G SENSOR 1
COMMON 1, SENSOR AND TEST
T SENSOR 1
OUTPUT 1 DIFFERENTIAL INTENSITY TEST
1 AUX
VOLTAGE-FREE CONTACT RELAY N/C (CONNECTION N/C WITH 2)
2 AUX
VOLTAGE-FREE CONTACT RELAY N/C (CONNECTION N/C WITH 1)
(Opens contact between 1 and 2 in the event of alarm and locking)
-
Description of module’s front connection terminals (U-type terminals)
I SENSOR 1
INPUT 1 DIFFERENTIAL INTENSITY SENSOR
G SENSOR 1
COMMON 1, SENSOR AND TEST
T SENSOR 1
OUTPUT 1 DIFFERENTIAL INTENSITY TEST
1 AUX. IN-OUT
DO NOT CONNECT
2 AUX. IN-OUT
VOLTAGE-FREE CONTACT RELAY N/C
(the ancillary relay is enabled in event of locking)
3 AUX. IN-OUT
VOLTAGE-FREE CONTACT RELAY COM
(the ancillary relay is enabled in event of locking)
4 AUX. IN-OUT
VOLTAGE-FREE CONTACT RELAY N/A
(the ancillary relay is enabled in event of locking)
5 AUX. IN-OUT
DO NOT CONNECT
6 AUX. IN-OUT
DO NOT CONNECT
7 AUX. IN-OUT
DO NOT CONNECT
8 AUX. IN-OUT
INPUT FOR EXTERNAL POTENTIAL-FREE CONTACT (REMOTE IN)
9 AUX. IN-OUT
INPUT FOR EXTERNAL POTENTIAL-FREE CONTACT (REMOTE IN)
IN ORDER TO ORDER EXTERNALLY A DISCONNECTION, UNLOCKING OR RESET TO ZERO OF THE TRIPPING COUNTER, CLOSE THE
CIRCUIT BETWEEN 8 AUX. IN-OUT AND 9 AUX. IN-OUT DURING ONE SECOND AND THEN RE-OPEN.
8 AUX. IN-OUT AND 9 AUX. IN-OUT ARE TO BE CONNECTED AND DISCONNECTED BY MEANS OF A RELAY WITH POTENTIAL-FREE
CONTACTS AND WITH AN ISOLATION POTENTIAL OF 4KV
- Other options input output remote control, please consult