40
1
3
2
D
SafeLine SL6+ v.3.9.0 EN
The SL6+ system can be used as a firefighter
intercom system. Depending on the configu-
ration, you can have up to 6 voice stations as
fire units. Start Fire Mode by activating input 2
(default) on the main unit. Refer to the "Wiring
diagram SL6+ main unit".
Configuration
Use SafeLine Pro, LYNX or parameter *73* (please refer to the
corresponding code in the ”Parameter List”) to configure the units
for Fire mode.
• Set Input 1 to Fire mode: *73*14#.
• Set Input 2 to Fire mode: *73*24# - default.
• Select other voice stations to be included in Fire mode with SL
Pro.
Operation
Activating Fire mode does the following:
A siren sound is heard in the speaker of the main unit during the
active time. Press the reset button to stop the siren sound. A voice
message specifically for Fire mode is played. Refer to the ”Distress
message”-section of the ”Parameter List” table. When Fire mode is
activated the units operate as intercom units only and can not make
emergency calls.
Voice communication
• Voice station in the car: microphone and speaker are both
active.
• Other units: the alarm button has the “Push to talk/Release to
listen”-function.
• A short beep is heard when you press/release the button.
• When in Fire mode, use the configuration handset to
participate in an intercom conversation.
• The yellow pictogram lights up when Fire mode is activated.
• The green pictogram lights up when in speech mode and is
out when listening.
• End Fire mode by disabling the input (1 or 2) on the main unit
configured for Fire mode.
Fire mode
Input 2 (configurable)
Input 1 (configurable)
+12 VDC