Operating
The SL6+ system can be used as a firefighter
intercom system. Depending on the configuration,
you can have up to 6 voice stations as fire units.
Start Fire Mode by activating input 2 (default)
on the main unit. Refer to the
"Wiring diagram SL6+ main unit" (page 10).
Configuration
Use SafeLine Pro, CONNECT or parameter *73* (please refer to the corre-
sponding code in the ”Parameter List”) to configure the units for Fire mode.
• Set Input 1 to Fire mode: *73*14#.
• Set Input 2 to Fire mode: *73*24# - default.
• Select other voice stations to be included in Fire mode with SL Pro.
Operation
Activating Fire mode does the following:
A siren sound is heard in the speaker of the main unit during the active
time. Press the reset button to stop the siren sound.
A voice message specifically for Fire mode is played. Refer to the
”Distress message”-section of the ”Parameter List” table.
When Fire mode is activated the units operate as intercom units only
and can not make emergency calls.
Voice communication
• Voice station in the car: microphone and speaker are both active.
• Other units: the alarm button has the “Push to talk/Release to
listen”-function.
• A short beep is heard when you press/release the button.
• When in Fire mode, use the configuration handset to
participate in an intercom conversation.
• The yellow pictogram lights up when Fire mode is activated.
• The green pictogram lights up when in speech mode and is out when
listening.
• End Fire mode by disabling the input (1 or 2) on the main unit
configured for Fire mode.
Fire mode
INPUT 2 (configurable)
INPUT 1 (configurable)
+12 VDC