1. Software version
(Cannot be changed).
2. Refrigerant.
0. Uninitialized
(Note! Do not select the shaded
fields).
1. R717
2. R22
3. Compressor type.
0. Uninitialized
1. SAB 110S
2. SAB 110L
3. SAB 128H Mk 1
4. SAB 128H Mk 2
5. SAB 163H Mk 1
6. SAB 163B Mk 1
7. SAB 163H Mk 2
8. VMY Mk 1, 2, 2.5
9. VMY 347H
10. VMY 347M
11. VMY 447H
12. VMY 447M
4. Prelubrication.
0. No
1. Yes
5. Booster operation.
0. No
1. Yes
6. Automatic V
i
regulation.
0. No
1. Yes
For more information, please refer
to
Variable volume control.
7. HLI/BLI set point (--20
°
C - +150
°
C).
This parameter specifies the dis-
charge temperature above which the
HLI/BLI relay is energized.
If 100 is entered, the function is dis-
abled.
8. Economizer.
0. No
1. Yes
9. Economizer (--60
°
C - +25
°
C).
High limit for suction pressure. The
economizer is activated only when
the suction pressure falls below this
value (
°
C
sat
).
10. Economizer (0% - 100%).
Low limit for capacity. The econo-
mizer is activated only when the ca-
pacity exceeds this value. It is not ac-
tivated when the capacity falls 20%
below this value.
11. Swept volume.
The value must be entered in tens of
m
3
/h and is displayed as such.
UNISAB S-Control selects a standard
value for the compressor based on fe-
male drive. Always check that this
value is correct.