Alarm/warning functions
Alarms
When an alarm limit is exceeded the com-
pressor stops. The relevant LED will flash
quickly and the alarm relay will change to
alarm position.
The cause of the excessive temperature/
pressure must be corrected and the value
brought within the warning limit before the
alarm can be cancelled. Please refer to the
section
Warning limits
.
The compressor can now restart in two dif-
ferent ways -- some of the alarms by
auto-
matic reset
and some by
manual reset
.
·
At manual reset the compressor can only
start when the reason for stopping has
been rectified and the actual value is
once again within the
warning limit
and
the
RE-
SET
key has been pressed. Please re-
fer to the section
Warning limits
.
·
At automatic reset the compressor can
restart when the actual value is again
within the
warning limit
(i.e. it is not
necessary to press the
RE-
SET
key).
In the following table manual reset is in-
dicated by
M
, and automatic reset by
A
.
Suction pressure
Discharge pressure
Superheat
Discharge temp.
Oil temperature
Brine temperature
Low
High
¯
A
A
M
M
M
M
M
M
M
M
Set Point
Set Point
Diff. pressure
M
M