4. Diagnostics
ROS® v3.11User Guide
91
RMC30
Default: sys_alarm
The alarm name (e.g. as obtained via CLI:"alarms")
Level
Synopsis: { EMRG, ALRT, CRIT, ERRO, WARN, NOTE, INFO, DEBG }
Severity level of the alarm:
• EMERG - The device has had a serious failure that caused a system reboot.
• ALERT - The device has had a serious failure that did not cause a system reboot.
• CRITICAL - The device has a serious unrecoverable problem.
• ERROR - The device has a recoverable problem that does not seriously affect operation.
• WARNING - Possibly serious problem affecting overall system operation.
• NOTIFY - Condition detected that is not expected or not allowed.
• INFO - Event which is a part of normal operation, e.g. cold start, user login etc.
• DEBUG - Intended for factory troubleshooting only.
Latch
Synopsis: { On, Off }
Default: Off
Enables latching occurrence of this alarm in the Alarms Table.
Trap
Synopsis: { On, Off }
Default: Off
Enables sending an SNMP trap for this alarm.
Log
Synopsis: { On, Off }
Default: Off
Enables logging the occurrence of this alarm in syslog.txt.
LED & Relay
Synopsis: { On, Off }
Default: Off
Enables LED and fail-safe relay control for this alarm. If latching is not enabled, this field
will remain disabled.
Refresh Time
Synopsis: 0 s to 60 s
Default: 60 s
Refreshing time for this alarm.
4.1.5. Viewing and Clearing Alarms
Alarms are displayed in the order in which they occurred, even if the real time clock was
incorrect at the time of the alarm.