2. Serial Protocols
ROS® v3.11User Guide
67
RMC30
The remote port number at which the Modbus protocol makes TCP connection requests.
Forward Exceptions
Synopsis: { Disabled, Enabled }
Default: Enabled
Enables forwarding exception messages to the Master as exception codes 10 (no path) or
11 (no response) When the Master polls for an unconfigured RTU or the remote Modbus
Server receives a poll for an RTU which is not configured or is timing out, it returns an
exception message. Disable this feature if your Master does not support exceptions but
recognizes failure by time-out when waiting for response.
Link Stats
Synopsis: { Disabled, Enabled }
Default: Enabled
Enables link statistics collection for this protocol.
DSCP
Synopsis: 0 to 63
Default: 0
To set the DS byte in the IP header. DS byte setting is supported in the egress direction
only.
2.3.7. WIN and TIN
Figure 2.21. WIN and TIN Form