Circulation
Arrangement / opt. functions / Add new function / Circulation
Adjustment
channel
Description
Adjustment range / selection
Factory setting
Relay
Relay selection
system dependent
system dependent
Type
Variant
Demand, Thermal, Timer,
Therm.+Timer, Timer
Thermal
Sensor
Circulation sensor selection system dependent
system dependent
Ton
Switch-on temperature
10 … 59 °C
40 °C
Toff
Switch-off temperature
11 … 60 °C
45 °C
Timer
Timer sub-menu
-
-
Days of the
week
Day selection
All days, Monday … Sunday,
Continue
-
Timer
Time frame adjustment
00:00 … 23:45
-
Sensor
FS08 sensor input selection system dependent
system dependent
Delay
Demand switch-on delay
0 … 2 s
1 s
Runtime
Circulation pump runtime
01:00 … 15:00 min
03:00 min
Break time Circulation pump break time 10 … 60 min
30 min
Funct.
Activation / Deactivation
Activated, Deactivated
Deactivated
The Circulation function can be used for controlling a circulation pump.
For the control logic, 5 different variants are available:
• Thermal
• Timer
• T Timer
• Demand
• Timer
If one of the variants is selected, the corresponding adjustment channels will appear.
Thermal
The temperature at the allocated sensor is monitored. The allocated relay switches
on when the temperature falls below the adjusted switch-on temperature. If the
temperature exceeds the switch-off temperature, the relay switches off.
Timer
The relay is switched on during the adjusted time frames, outside of them it switch-
es off. For information on how to adjust the timer, see below.
Thermal + Timer
The relay operates when the switch-on conditions of both above mentioned var-
iants are fulfi lled.
Relay
Sensor
Circulation