When the Timer option is activated, a timer is indicated in which time frames for
the function can be adjusted.
Note:
For information on timer adjustment see page 11.
Sen. Source
Sen. Sink
Relay
Solid fuel boiler
Arrangement / opt. functions / Add new function / Solid fuel boiler
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Relay
Relay selection
system dependent
system dependent
Sen. Boiler Solid fuel boiler sensor selection
system dependent
system dependent
Sen. Store Store sensor selection
system dependent
system dependent
∆
Ton
Switch-on temperature difference
1.0 … 30.0 K
6.0 K
∆
Toff
Switch-off temperature difference
0.5 … 29.5 K
4.0 K
∆
Tset
Set temperature difference
1.5 … 40.0 K
10.0 K
Min. speed Minimum speed
(20) 30 … 100 %
30 %
Tmax St.
Maximum temperature
10 … 95 °C
60 °C
Tmin boiler Minimum temperature
10 … 95 °C
60 °C
Funct.
Activation / Deactivation
Activated, Deactivated Deactivated
The Solid fuel boiler function can be used for transferring heat from a solid fuel
boiler to a store. The allocated relay is energised when all switch-on conditions
are fulfi lled:
• the temperature difference between the allocated sensors has exceeded the
switch-on temperature difference
• the temperature at the solid fuel boiler sensor has exceeded the minimum
temperature
• the temperature at the store sensor has fallen below the maximum temperature
When the Set temperature difference is exceeded, pump speed control starts. For
every deviation of 0.2 K, the pump speed will be adjusted by 1 %.
Boiler sensor
Store sensor
Relay