53
en
Arrangement / opt. functions / Add new function / Function block
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Relay
Relay selection
system dependent
system dependent
Thermostat a Thermostat a
Yes, No
No
Th-a on
Switch-on temperature Thermostat a -40 … +250 °C
+40 °C
Th-a off
Switch-off temperature Thermostat a -40 … +250 °C
+45 °C
Sensor
Sensor thermostat a
system dependent
system dependent
Thermostat b Thermostat b
Yes, No
No
Th-b on
Switch-on temperature Thermostat b -40 … +250 °C
+40 °C
Th-b off
Switch-off temperature Thermostat b -40 … +250 °C
+45 °C
Sensor
Sensor thermostat b
system dependent
system dependent
∆
T function Differential function
Yes, No
No
∆
Ton
Switch-on temperature difference
1.0 … 50.0 K
5.0 K
∆
Toff
Switch-off temperature difference
0.5 … 49.5 K
3.0 K
∆
Tset
Set temperature difference
3 … 100 K
10 K
Min. speed
Minimum speed
(20) 30 … 100 %
30 %
Sen. Source Heat source sensor
system dependent
system dependent
Sen. Sink
Heat sink sensor
system dependent
system dependent
Timer
Timer sub-menu
-
No
Days of the
week
Day selection
All days, Monday …
Sunday, Continue
-
Timer
Time frame adjustment
00:00 … 23:45
-
Ref. relay
Reference relay
Yes, No
No
Mode
Reference relay mode
OR, AND
OR
Relay
Reference relay 1
all relays*
-
Relay
Reference relay 2
all relays*
-
Relay
Reference relay 3
all relays*
-
Relay
Reference relay 4
all relays*
-
Relay
Reference relay 5
all relays*
-
Funct.
Activation / Deactivation
Activated, Deactivated Activated
* Relays that have been selected as parallel relays (in the optional functions Solar/Parallel
relay and Arrangement/Parallel relay) will not work as reference relays.
Irradiation switch
Arrangement / opt. functions / Add new function / Irrad. switch
Adjustment
channel
Description
Adjustment range / selection Factory setting
Relay
Relay selection
system dependent
system dependent
Irrad.
Switch-on irradiation
50 … 1000 W / m²
200 W / m²
Duration
Switch-on duration
0 … 30 min
2 min
Inverted
Inverted switching option
Yes, No
No
Funct.
Activation / Deactivation
Activated, Deactivated
Deactivated
The Irrad. switch function can be used for operating a relay depending on the
measured irradiation value.
The allocated relay is switched on if the adjusted irradiation value remains exceed-
ed for the adjusted duration. If the irradiation falls below the adjusted value for the
adjusted duration, the relay is switched off.
If the Inverted option is activated, the relay operates vice versa.