BA054BB1117A6
23
EC-Regler schaltet ab
¤)
Alarm muss durch ca. 60 Sek.
langes Abschalten des EC-
Reglers vom Netz rückgestellt
werden.
Min. 2 Phasen an den
Motorklemmen sind kurz-
geschlossen
Kurzschluss an den Motorklemmen beheben ¤)
Defekter Motor
Motor austauschen ¤)
Überbelasteter Motor
Motor entlasten ¤)
Laufrad hat falsche Dreh-
richtung
Drehrichtung prüfen und ggf. Phasen zwischen
EC-Regler und Motor tauschen. ¤)
Laufrad streift
Laufrad streift an Düse
Düse ausrichten
Schmutz
Laufrad auf Fremdkörper und Rundlauf untersu-
chen, Befestigungen am Laufrad und an der
Düse kontrollieren.
Vibrationen / Geräusche im
Ventilator
Verschmutzung des Lauf-
rades
Laufrad säubern
Lagerschaden
Motor sofort stillsetzen und Rosenberg After
Sales Service kontaktieren.
Fault
Possible cause
Action
Motor inoperative
No supply voltage
Check that the power supply is correctly con-
nected to the EC Controller (terminals "L" and
"N" for 230 V models and terminals "L1", "L2"
and "L3" for 3 x 400 V and 3 x 230 V models).
Poor electrical connec-
tions
Check pin connectors and all other electrical
connections.
No enable signal
Check connection between 8 and 10
No 0-10 V DC control
signal
Check that the 0-10 V DC control signal is con-
nected correctly
No 0-10 V DC control
signal
Alarm relay is mishandled.
With potentiometer control:
Check that the potentiometer's 0-10 V DC con-
trol signal is connected
correctly The potentiometer must have an inter-
nal re
sistance of at least 4 kΩ.
Check function of the alarm relay.
The motor has been
stopped by the built-in
motor protector 5 times
cause of overload or other
alarm.
The alarm can be reseted by disconnecting the
power supply to the OJ-EC and reconnecting it
after approx. 60 seconds.
Locked impeller
Check impeller for foreign object or dirt damage.
failure reset
Defective EC Controller
Replace EC Controller
Defective motor
Replace motor
Impeller has wrong direction of
rotation
Phases between EC-
controller and motor
swapped
Check direction of rotation and swap if neces-
sary phases between EC-controller and motor.
Summary of Contents for GK CE Series
Page 29: ...BA054BB1117A6 29...