Operation
54 / 89
Operation
► Press
Scroll back screen page
or
Scroll forward screen page
function
switch to display the
Operating hours
screen page.
Operating hours
screen page appears on the display.
Operating hours screen page
► Press the
Confirm message
function switch for approx. 5 seconds.
An ISO error test is performed.
The following symbol appears on the screen if a protective earth con-
nection is present.
The consumer can be used.
If this message does not appear, this signals a faulty protective con-
nector connection.
► Do not use the consumer.
7.6.3
Connect consumer
DANGER!
Mortal danger or serious injury from electric shock!
Observe the safety distance from voltage-carrying parts at all times.
Only use consumers in flawless technical condition.
Do not earth power generator.
Do not connect the ground wire to an existing equipotential bonding
conductor.
Do not connect the power generator to an existing power network.
Power decrease
The full power can only be drawn with uniform, three-phase phase load. For
single-phase consumers, only one third of the rated power per phase can
be drawn.
See chapter "Technical data".
When using extension cables or mobile distribution networks:
•
max. 60 m (at 1.5 mm
2
)
1
•
max. 100 m (at 2.5 mm
2
)
2
The power generator is designed for mobile use with one or more elec-
trical consumers.
Safety isolation according to VDE 100, Part 551
The protective earth conductor of the earthing contact plug assumes
the function of the equipotential bonding conductor.
The current is drawn as standard from sockets with a nominal voltage
of 230/400 V 50 Hz.
1
max. 45 m (at 1.5 mm²) at special voltage 130/225 V. Observe sticker under the socket.
2
max. 75 m (at 2.5 mm²) at special voltage 130/225 V. Observe sticker under the socket.