Factory settings
Page 52
RES-445
11
Factory settings
The RESISTRON temperature controller RES-445 is
configured in the factory as follows:
The controller can be reset with step 21 in the
Configuration menu:
The factory settings are restored if the "ENTER" key is
pressed. An acknowledgment message is displayed for
approximately 2s.
DIP switches
for
secondary voltage
U
2
and current I
2
U
2
= 6…60VAC
I
2
= 30…100A
DIP switches:
2 ON
1, 3, 4, 5 OFF
Values in the Settings
and Configuration
menus
Settings menu
Step 1
Heatsealing temperature: 0°C
Step 2
Preheating temperature: 0°C
Step 3
Starting delay:
0s
Step 4
Heatsealing time:
1s
Step 5
Cooling value:
Cooling time:
10 s
Absolute cooling temperature:50°C
Relative cooling temperature: 40 % of
heatsealing
temperature
Step 6
Hold mode:
OFF
Step 7
AUTOCAL temperature: 20°C
Configuration menu
Step 20 Language
German
This selection is NOT changed if the
factory settings are restored with step 21
in the Configuration menu.
Step 22 Alloy/range:
Alloy-20/max. 300°C
Step 23 Maximum temperature: 300°C
Step 24 Set point reached:
-10K
Step 25 Set point exceeded:
+10K
Step 26 Time control:
OFF
Step 27 Cooling mode:
Absolute
Step 28 Start of heatsealing time: When temperature reached
Step 29 Relay K1 function:
Active when temperature reached
Step 30 Cycle counter:
0
Step 31 Alarm relay:
Normal (contact closed by alarm)
Step 32 Measuring impulse length:Standard (1.7ms)
Step 33 Analog output:
Actual temperature
3
2
1
4 5
ON
OFF