Controller functions
RES-445
Page 29
5
Cooling value
The cooling value can be specified here according
to the cooling mode (absolute, relative, time)
selected with step 27.
• Absolute: The cycle ends if the "cooling
temperature" falls below the set value (in °C).
50°C to maximum
temperature (step 23)
• Relative: The cycle ends if the "cooling
temperature" falls below the set percentage
value, whereby 100% corresponds to the
specified set point (step 1).
40%…100%
• Time: The cycle ends when the set "cooling
time" in seconds has elapsed. The current
cooling value is indicated in the home position.
This function can only be selected if time control
(step 26) is active.
0…99.9s
6
Hold mode
If the "Hold" function is activated, the last measured
value at the end of the heating phase is stored and
displayed.
The "ACT" (actual value) information in the home
position is replaced by "Hold". This procedure is
repeated for every cycle and the displayed value is
updated. The word "Hold" is invisible for 100ms
before the value is updated.
If you select the "2 second hold" function, the
display changes back from hold mode to the actual
value in real time after 2 seconds. The hold function
is then activated again for 2 seconds at the end of
the next cycle.
ON
OFF
2 s
7
Autocal
The AUTOCAL function matches the controller to
the current and voltage signals that are present in
the system.
The required calibration temperature can be set
with the "UP" and "DOWN" keys. Pressing the
"ENTER" key stores the set value and starts the
"AUTOCAL" function.
The word "- Calibration -" appears on the display
while the AUTOCAL function is executing and a
counter counts down from 13 to 0. When the
controller has been calibrated successfully, the
display switches back directly to the home position.
If the controller cannot be calibrated, the AUTOCAL
function is aborted and an error message is
displayed instead.
0…40°C
No.
Name
Description
Setting range