Page 64
Bit 11 = High[1]
Definite time OVGR[64G]
Bit 12 = High[1]
Instantaneous OVGR[64G]
Bit 13 = High[1]
Definite time SGR[67G]
Bit 14 = High[1]
Definite time SGR2[67G]
Bit 15 = High[1]
Definite time GR
T15 : Captured Waveform Data Scale
†
(INT16)
Value
‡
Scale
Descriptions
0-3
2.2
Select voltage channel
4-7
0.22
Select current channel
†
Captured Waveform Data(address 42111-42436) must be multiplied by a scale of a certain value for each,
and the value varies depending on the value of the selected channel (address 42106).
‡
Selected channel (address 42106).
T16 : Fault, Pickup Status 2
Value
Descriptions
0x0000
None
Bit 0 = High[1]
Inverse OCGR2
Bit 1 = High[1]
Definite time UVR2
Bit 2 = High[1]
Definite time UVR3
Bit 3 = High[1]
Inverse NSOCR
Bit 4 = High[1]
Instantaneous, Definite time NSOCR
Bit 5 = High[1]
THR
Bit 6 = High[1]
51LR
Bit 7 = High[1]
Starting motor
Bit 8 = High[1]
UCR
Bit 9 = High[1]
Definite time NSOVR
T17 : DIN Input Type Setup
Value
Descriptions
0x0000
Non-inverting
0x0001
Inverting