Page 42
Auxiliary Function 1 Setup section
Address
Attribute
Measurement
Format
Descriptions
Clock
43001-
43002
R/W
New Date
UINT32
Refer to “Value Table T1”
43003-
43004
R/W
New Time
UINT32
Refer to “Value Table T2”
43005
R/W
Clock Save Request
(Save Address : 43001 - 43004)
UINT16
0x00FF = Save Request
0x0000 = Do not save
LCD
43006
R/W
Backlight On time on LCD
UINT16
1 - 60 min
43007
R/W
Contrast on LCD
UINT16
10 - 250 / 10
43008
R/W
Save Request on LCD
(Save Address : 43006 - 43007, 43010)
UINT16
0x00FF = Save Request
0x0000 = Do not save
Pass Code
43009
R
Pass Code
UINT16
LCD Korean Font
43010
R/W
Korean font on LCD
UINT16
1 = Type1
2 = Type2
3 = Type3
•••
Invalid
UINT16
•••
43030
Invalid
UINT16