Page 41
Captured (Event) Waveform section
†
Address
Attribute
Measurement
Format
Descriptions
Captured Waveform information
42101
R
Number of Captured Waveform
UINT16
0 - 4
42102
R
Event record number of Captured
Waveform
UINT16
1 - 600
42103
Reserved
UINT16
42104
Reserved
UINT16
Captured Waveform Number selector
42105
R/W
Selected Waveform number
UINT16
0 - 4
42106
R/W
Selected Channel
UINT16
0 = Va
1 = Vb
2 = Vc
3 = Vg
4 = Ia
5 = Ib
6 = Ic
7 = Ig
42107
R
Reserved
UINT16
42108
R/W
Captured Waveform data Update Request
UINT16
Write(0x00FF) = Update Request
Read(0x0000) = Update Done
42109
R
Reserved
UINT16
42110
R
Reserved
UINT16
Captured Waveform Data
42111-
42112
R
Date of Selected Waveform
UINT32
Refer to “Value Table T1”
42113-
42114
R
Time of Selected Waveform
UINT32
Refer to “Value Table
T2”
42115
R
Cause of Selected Waveform
UINT16
4 = Pickup
42116
R
Reserved
UINT16
42117
R
1
st
Data of Selected Cycle
INT16
Refer to “Value Table T5”
42118
R
2
nd
Data of Selected Cycle
INT16
Refer to “Value Table T5”
•••
•••
INT16
42435
R
319
th
Data of Selected Cycle
INT16
Refer to “Value Table T5”
42436
R
320
th
Data of Selected Cycle
INT16
Refer to “Value Table T5”
•••
Invalid
UINT16
•••
43000
Invalid
UINT16
†
In the captured waveform data, only the waveform of the first event is stored when the time interval of the
events (Pickup, Alarm, Trip, Trip & Alarm) storing the waveform is less than 160 milliseconds.
†
When more than 5 events occur, the old data is changed to the new waveform data with the FIFO (First In
First Out) method.
†
Captured Waveform Data is recorded in volatile memory and erased when power is not supplied.